Technical parameters compiled from the manufacturer data sheet and reference documentation.
| Technical Specifications |
| Other |
| Number of inputs |
4 |
| Power supply |
via the E-bus |
| Distributed clocks |
– |
| Input filter cut-off frequency |
typ. 1 kHz |
| Connection technology |
2-wire |
| Conversion time |
approx. 1.6 s up to 12 ms, depending on configuration and filter setting, default: approx. 165 ms |
| Voltage measurement |
±78 mV |
| Resolution |
24 bit, presentation adjustable: 0.1/0.01/0.001°C per digit or 10 nV per digit |
| Temperature measurement (thermocouple) |
type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) |
| Measurement uncertainty (temperature measurement) |
at 23°C ambient temperature, with internal cold junction, according type: B: ±2.6°C; C: ±2.2°C; E: ±1.6°C; J: ±1.6°C; K: ±1.6°C; L: ±1.5°C; N: ±1.6°C; R: ±2.2°C; S: ±2.3°C; T: ±1.6°C; U: ±1.5°C; for further details see documentation |
| Electrical isolation |
500 V (E-bus/signal voltage) |
| Current consumption E-bus |
typ. 200 mA |
| Current consumption power contacts |
– |
| Special features |
channel by channel wire break detection, internal and external cold junction, firmware filter adjustable |
| Weight |
approx. 60 g |
| Operating temperature |
-25…+60°C |
| Storage temperature |
-40…+85°C |
| Relative humidity |
95%, no condensation |
| Vibration/shock resistance |
conforms to EN 61000-6-2/EN 61000-6-4 |
| EMC immunity/emission |
conforms to EN 60068-2-6/EN 60068-2-27 |
| Protect. rating/installation pos. |
IP20/variable (see documentation) |
| Approvals/markings |
CE, CCC, UL, ATEX, IECEx, cFMus |
| Ex marking |
ATEX: II 3G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
| Design form |
compact terminal housing with signal LEDs |
| Material |
polycarbonate |
| Side by side mounting by means of |
double slot and key connection |
| Wiring |
solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
| Connection cross-section |
s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
| Connection cross-section AWG |
s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
| Stripping length |
8…9 mm |
| Current load power contacts |
Imax: 10 A |
| Dimensions (W x H x D) |
12 mm x 100 mm x 68 mm |
| REACH SVHC |
no |
| POP |
compliant |
| RoHS |
compliant with exemption |
| CA Prop65 |
www.beckhoff.com/prop65 |
Model variants, options and firmware revisions can affect fitment. Before ordering the Beckhoff EL3314-0010 ethercat terminal, share your existing part number or project requirements and our team will cross-reference comparable in-stock Beckhoff units and verify compatibility. This listing is provided by an independent industrial-automation distributor; brand names and part numbers are used for identification only.
Independent supplier: Beckhoff part EL3314-0010 is supplied by SHLY-PLC, an independent industrial-automation distributor. Brand names and part numbers are used for product identification and remain the property of their respective owners; this listing is not affiliated with, sponsored or endorsed by the manufacturer.
A: Each EL3314-0010 is inspected and functionally checked before sale. Contact us for the current stock condition and quantity.
A: In-stock orders placed before 14:00 ship the same business day. Standard worldwide delivery is about 5-8 business days, express shipping is available and orders over $500 ship free.
A: Yes. Share your existing part number or application and our technical team will verify compatibility and provide cross-references to comparable in-stock models.