MVI69-MNETC ProSoft Modbus TCP/IP Multi-Client Communication Module for 1769 CompactLogix
The ProSoft Technology MVI69-MNETC is a single-slot 1769 backplane Modbus TCP/IP multi-client communication module for Rockwell CompactLogix and MicroLogix 1500 LRP controllers. It enables the CompactLogix system to operate as Modbus TCP client to read/write registers from multiple Modbus TCP server field devices, such as flow meters, transmitters, power meters and third-party PLCs. Technical data sourced from official ProSoft datasheet. Supplied by SHLY-PLC, an independent industrial automation distributor; each unit undergoes visual inspection and functional testing before shipment for retrofit and spare replacement projects. Contact our team for compatibility verification.
Features
-
Order Code: MVI69-MNETC
-
Product Family: MVI69 Series for 1769 CompactLogix
-
Primary Function: Modbus TCP/IP Multi-Client Module for 1769 backplane
-
Backplane: Single slot 1769 CompactLogix / MicroLogix 1500 LRP chassis mounting
-
Ethernet Port: 10/100 Base-T, auto crossover, galvanic isolation 1500 Vrms
-
Internal Database: Up to 5000 user-defined 16-bit registers for data exchange
-
Data Type: Supports coil, discrete input, holding register, input register; Enron/Daniel floating-point support
-
Configuration: ProSoft Configuration Builder (PCB), RS232 CFG debug port, Add-On Instruction (AOI) & sample ladder logic included
-
LED Status: Power, Module Status, Application, CFG port, Ethernet activity & fault LEDs
-
Lifecycle: Discontinued OEM production, aftermarket spare part only
-
Typical Use: CompactLogix acts as Modbus TCP client to connect multiple Modbus TCP servers, process plant retrofits, energy monitoring systems
Specifications
Official Datasheet Technical Parameters
| Technical Specifications |
| Catalog Number |
MVI69-MNETC |
| Hardware Type |
1769 Single-Slot Modbus TCP Multi-Client Module |
| Backplane Power |
800mA @ 5VDC, power supply distance rating 2 |
| Ethernet |
10/100 Base-T, auto MDI/MDIX, 1500V isolation |
| Register Database |
Max 5000 16-bit registers |
| Configuration Port |
RJ45 RS232 CFG debug port, RJ45 to DB9 cable included |
| Environmental Ratings |
| Operating Temperature |
0°C ~ +60°C (32°F ~ +140°F) |
| Storage Temperature |
-40°C ~ +85°C (-40°F ~ +185°F) |
| Relative Humidity |
5% ~ 95% RH, Non-Condensing |
Compatibility & Cross-References
The MVI69-MNETC is legacy Modbus TCP multi-client module for Rockwell 1769 CompactLogix / MicroLogix 1500 LRP rack. It functions as standard 1769 I/O module for the controller, utilizing AOI instructions to transfer tag data between PLC and module register database. This module is Client-only variant, different from MVI69-MNET which supports both Client & Server. This listing is provided by an independent industrial-automation distributor; brand names and part numbers are used for product identification only.
Applications
- CompactLogix as Modbus TCP client to read/write multiple remote Modbus TCP server instruments
- Energy monitoring, power meters, flow transmitters, temperature sensors integration
- Connect to third-party Modbus TCP PLCs, RTU gateways and SCADA slave devices
- Legacy automation system spare replacement and process control retrofit projects
Warranty
-
Availability: MVI69-MNETC discontinued OEM production, supply as aftermarket spare; contact us for real-time stock status.
-
Inspection & testing: each unit is visually inspected and functionally checked before packing.
-
Delivery: orders are processed within 2-4 business days after payment confirmation; standard worldwide delivery is about 5-8 business days, express shipping available, orders over $500 ship free.
Warranty: 12-month seller warranty provided by SHLY-PLC. See our Return Policy for coverage and claims.
Independent supplier: ProSoft Technology part MVI69-MNETC is supplied by SHLY-PLC, an independent industrial automation distributor. Brand names and part numbers are used for product identification and remain the property of their respective owners; this listing is not affiliated with, sponsored or endorsed by the manufacturer.
Frequently Asked Questions
Q: What is MVI69-MNETC?
A: MVI69-MNETC is ProSoft Modbus TCP/IP Multi-Client communication module for Rockwell 1769 CompactLogix / MicroLogix 1500 LRP backplane.
Q: What is the difference between MVI69-MNETC and MVI69-MNET?
A: MVI69-MNETC is Client only. MVI69-MNET supports both Modbus TCP Client and Server functions.
Q: What software configures this module?
A: ProSoft Configuration Builder (PCB) for network setup; Studio 5000 / RSLogix5000 with supplied AOI for backplane tag mapping.
MVI69-MNETC · Technical reference data · Independently supplied by SHLY-PLC