The ProSoft MVI56-HART is a communication module for industrial automation and control systems. It is supplied by SHLY-PLC, an independent industrial-automation distributor: every unit is visually inspected and functionally checked before dispatch, held in ready stock and shipped worldwide for maintenance, spares and retrofit use. Share your application or existing part number and our team will confirm fitment and comparable in-stock alternatives.
Specifications
Technical parameters compiled from the manufacturer data sheet and reference documentation.
| Key Specifications |
| Number of Channels |
4 |
| ADC Resolution |
12 bit |
| Input Impedence |
247.5 Ω |
| Accuracy (Calibrated 25°C) |
< 0.15 % |
| Accuracy (Uncalibrated) |
< 0.30 % |
| Range |
0 to 22 mA |
| Current limit |
34 mA |
| Connector |
RJ45 |
| Type Designation |
| Order code |
MVI56-HART |
| Product family / base order code |
MVI56 |
| Version / revision suffix |
HART |
| Power Supply |
| Current limit |
34 mA |
| Power Requirements |
12 to 28 VDC35mA @ 24 VDC - With no field devices attached130mA @ 24 VDC - With 4 field devices at 22mA each64mA @12 VDC - With no field devices attached160mA @ 12 VDC - With 4 field devices at 22mA each |
| Power Consumption |
0.9 W - With no field devices attached 3.1 W - With 4 field devices at 22mA each4.3 W - With input channels shorted |
| Power Connector |
3-way terminal |
| Ports & Connections |
| Number of Channels |
4 |
| Input Impedence |
247.5 Ω |
| ARP Connections |
Max 20 |
| TCP Connections |
Max 20 |
| CIP Connections |
Max 10 |
| Function CodesSupported |
1: Read Coils 2: Read Discrete Inputs 3: Read Holding Registers4: Read Input Registers |
| Mode Supported |
DNP3 Outstation |
| Application Functions Supported |
Read Write Select/Operate Direct-Operate Direct-Operate-No-Response Authentication RequestAuthentication Response |
| Features & Protocols |
| Accuracy (Calibrated 25°C) |
< 0.15 % |
| Accuracy (Uncalibrated) |
< 0.30 % |
| Duplex Mode |
Full / Half |
| Function CodesSupported |
1: Read Coils 2: Read Discrete Inputs 3: Read Holding Registers4: Read Input Registers |
| Mode Supported |
DNP3 Outstation |
| Application Functions Supported |
Read Write Select/Operate Direct-Operate Direct-Operate-No-Response Authentication RequestAuthentication Response |
| Aggressive Mode Supported |
No |
| Mechanical & Environmental |
| Enclosure Rating |
IP20, NEMA/UL Open Type |
| Temperature |
-20 to 70 °C |
| Enclosure |
Plastic |
| Dimensions (H x W x D) |
101 x 22.5 x 120 mm |
| Compliance, Approvals & Standards |
| Product approvals |
CE, UKCA, UL/cUL, RoHS |
| EMC |
EN 61000-6-x / EN 55011 (industrial environment) |
| Safety standard |
IEC/EN 61131 / 61800 / 60947 (product-specific) |
Compatibility & Cross-References
-
Connector: RJ45
-
Power Connector: 3-way terminal
- Cross-references: send your existing part number or application and our technical team confirms fitment, protocol and wiring before you order.
Applications
- The ProSoft MVI56-HART is widely used to connect field I/O and serial devices to Ethernet and fieldbus control networks.
- Typical uses include protocol linking, device-level data acquisition and SCADA/HMI integration.
- It is deployed on conveyor lines, process skids and remote I/O stations where line topology reduces switching hardware.
- Engineers also specify it for machine retrofits and as a network interface between legacy and modern controls.
Ordering, Delivery & Warranty
-
Availability: Worldwide shipping.
-
Delivery: Orders are processed within 2-4 business days after payment confirmation; worldwide delivery typically takes 5-8 business days, express service is available and shipping is free on orders over $500.
-
Condition & testing: Each unit is visually inspected and functionally checked before dispatch and packaged for protective international transit.
Warranty: 12-month seller warranty provided by SHLY-PLC. See our Return Policy for coverage and claims.
Independent supplier: ProSoft part MVI56-HART is supplied by SHLY-PLC, an independent industrial-automation distributor. Brand names and part numbers are used for product identification and remain the property of their respective owners; this listing is not affiliated with, sponsored or endorsed by the manufacturer.
Frequently Asked Questions
Q: What condition is the MVI56-HART supplied in?
A: Each MVI56-HART is inspected and functionally checked before sale. Contact us for the current stock condition and quantity.
Q: How quickly can the MVI56-HART ship?
A: Orders are processed within 2-4 business days after payment confirmation. Standard worldwide delivery is about 5-8 business days, express shipping is available and orders over $500 ship free.
Q: Can you confirm compatibility or a replacement for the MVI56-HART?
A: Yes. Share your existing part number or application and our technical team will verify compatibility and provide cross-references to comparable in-stock models.
MVI56-HART · Technical reference data · Independently supplied by SHLY-PLC