Phoenix Contact · Hybrid motor starters
2900530 – ELR H3-SC- 24DC/500AC-9 · Hybrid motor starters
The Phoenix Contact 2900530 (ELR H3-SC- 24DC/500AC-9) is a Hybrid motor starters in the Phoenix Contact range. The specification below is transcribed from the official Phoenix Contact product page for this order number, which publishes the technical data in 12 sections: Product properties, Electrical properties, Input data, Output data, Connection data, Signaling and further sections.
Nominal voltage42 V AC ... 550 V AC
Degree of protectionIP20
Ambient temperature-25 °C ... 70 °C (observe derating)
Dimensions22.5 mm
ConnectionScrew connection
How it works
Phoenix Contact keeps the values in the groups shown below, in the order the manufacturer publishes them: Product properties, Electrical properties, Input data, Output data, Connection data, Signaling, Dimensions, Material specifications, Environmental and real-life conditions, Approvals, Standards and regulations, Mounting. The values are carried over unchanged from the official product page; nothing is added beyond what the manufacturer states for this order number.
Specifications
Product properties
Product typeHybrid motor starters
Product familyCONTACTRON
Operating mode100% operating factor
Electrical properties
Number of phases3
Motor starter typeDirect starter
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation for nominal condition13.5 W
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation14.6 W
Minimum power dissipation1.1 W
Coordination type1
Supply
Rated control circuit supply voltage U S24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current I S40 mA
Protective circuitSurge protection
ValueReverse polarity protection
Insulation characteristics
Rated insulation voltage500 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
ValueBasic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Input data
Control
Input nameControl input
Rated actuating voltage U C24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current I C5 mA (Input type 1)
Switching threshold9.6 V (“0” signal)
Value19.2 V (“1” signal)
Typical turn-off time< 30 ms
Protective circuitReverse polarity protection
Output data
AC output
Rated operating voltage U e500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current I e9 A (AC-51)
Value6.5 A (AC-53a)
Mains frequency50/60 Hz
Load current range0 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2-
Leakage current0 mA
Protective circuitSurge protection
Connection data
Control circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross-section rigid0.2 mm² ... 2.5 mm²
Conductor cross-section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm
Value5 lb f -in. ... 7 lb f -in.
Load circuit
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross-section rigid0.2 mm² ... 2.5 mm²
Conductor cross-section flexible0.2 mm² ... 2.5 mm²
Conductor cross-section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm
Value5 lb f -in. ... 7 lb f -in.
Signaling
Status displayLED (yellow)
Operating voltage displayGreen LED
Dimensions
Width22.5 mm
Height107 mm
Depth114 mm
Material specifications
Flammability rating according to UL 94 (Housing)V0 (Housing)
Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Approvals
UL approval
CertificateNLDX.E228652
UL data
SCCR100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
Value5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
FLA6.5 A (500 V AC)
Group installation20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Value30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category codeNLDX / NRNT
Standards and regulations
Standards/regulations
Standards/regulationsIEC 60947-1
ValueIEC 60947-4-2
ValueIEC 61508
ValueISO 13849
Mounting
Mounting typeDIN rail mounting
Assembly notealignable, for spacing see derating
Mounting positionvertical (horizontal DIN rail, motor output below)
Order number
2900530 — https://www.phoenixcontact.com/en-us/products/hybrid-motor-starter-elr-h3-sc-24dc500ac-9-2900530
Official source
Phoenix Contact official product page, technical data section (EN-US); order number 2900530.
FAQ
What voltage does the 2900530 operate at?
Phoenix Contact gives a nominal voltage of 24 V DC for this order number.
What degree of protection does the 2900530 have?
It is rated IP20, as stated in the official technical data.
What ambient temperature is permitted?
Phoenix Contact specifies an ambient temperature of -25 °C ... 70 °C (observe derating).
What are the dimensions?
The technical data gives 22.5 mm.
How is the 2900530 connected?
Phoenix Contact specifies the connection as Screw connection.