ABB · SACE Tmax XT
1SDA074744R1 is the ABB XT2N 125 TMA 100-500..1000 3p F F UL/CSA molded case circuit breaker: 3 poles, In = 100 A with a TMA thermal-magnetic adjustable trip unit, and fixed front (bolt-connected) terminals. It is used in UL489 panel feeders and distribution circuits where the installed unit is matched to the original catalog number.
-
Rated current In100 A
-
Trip unitTMA (thermal-magnetic)
-
Number of poles3 P
-
Rated operational voltage600 V AC / 500 V DC
Specifications
| Electrical |
| Frame / family |
SACE Tmax XT, XT2N 125 (125 A frame), UL/CSA version |
| Rated current In |
100 A (TMA overload setting 70...100 A) |
| Instantaneous setting Ii |
500...1000 A |
| Rated operational voltage Ue |
600 V AC / 500 V DC |
| Rated insulation voltage Ui |
1000 V |
| Rated impulse withstand Uimp |
8 kV |
| Breaking capacity Icu (UL489, AC) |
65 kA @ 240 V AC; 25 kA @ 480 V AC; 18 kA @ 600 V AC |
| Breaking capacity (UL489, DC) |
35 kA @ 250 V DC (2 poles in series); 35 kA @ 500 V DC (3 poles in series) |
| Short-circuit performance class |
N (IEC 60947-2: 36 kA @ 415 V AC) |
| Trip unit |
TMA thermal-magnetic, adjustable |
| Number of poles |
3 (3P) |
| Mechanical |
| Terminals |
Fixed front terminals (F F), bolt connection, M6, tightening torque 6 N·m |
| Dimensions / weight |
90 × 130 × 82.5 mm (W × H × D); 1.1 kg net |
| Compliance |
| Standards |
UL489 Listed, CSA certified (UL/CSA version); CE per EC Declaration of Conformity Tmax XT2 |
| Enclosure rating |
IP20 |
Values follow the ABB SACE Tmax XT UL/CSA catalog for catalog number 1SDA074744R1 (XT2N 125 TMA 100-500..1000 3p F F UL/CSA). This breaker has no communication ports. Parameters not confirmed for this variant are omitted rather than estimated.
Where it sits in the control system
The 1SDA074744R1 is a UL489 molded case circuit breaker for feeder and branch protection at up to 600 V AC / 500 V DC, with an 18 kA (600 V AC) UL489 interrupting rating. Lugs and terminal accessories are sized to the bolt-type fixed front terminals, and the trip settings (70...100 A overload, 500...1000 A instantaneous) are coordinated with the downstream conductors, not to a generic assumption.
Record the catalog number and revision from the nameplate of the installed unit before specifying a like-for-like spare.
Before you specify
-
Trip unit. The TMA thermal-magnetic trip is adjustable: 70...100 A (overload) and 500...1000 A (instantaneous). Set it to the conductor and load profile.
-
Breaking capacity. Confirm the installation's prospective fault current does not exceed the UL489 rating at the application voltage: 65 kA @ 240 V AC, 25 kA @ 480 V AC, 18 kA @ 600 V AC.
-
Poles. This catalog number is a 3-pole (3P) breaker. For DC applications, poles are connected in series as required by the DC interrupting rating.
-
Terminals. Fixed front bolt-type terminals (F F); verify lug size and terminal cover accessories before ordering.
Technical FAQ
Q.What supply does this device require?
It is rated for 600 V AC / 500 V DC operational voltage (Ui 1000 V). Size the installation to the same ratings shown in the Specifications table.
Q.What are the key electrical ratings?
In = 100 A (TMA, 70...100 A adjustable), Ii = 500...1000 A, 3 poles, UL489 Icu 65 kA @ 240 V AC / 25 kA @ 480 V AC / 18 kA @ 600 V AC. Cross-check them against the installed unit's nameplate.
Q.How is this device mounted?
Fixed mounting with bolt-type front terminals (F F). It is not a 35 mm DIN-rail MCB; plan the panel or plate mounting space for the 90 × 130 × 82.5 mm body.
Q.Does this breaker have communication ports?
No. The TMA thermal-magnetic version has no communication capability; communication accessories apply to electronic-trip XT2 variants, not this catalog number.
Q.What replaces a unit that is no longer in production?
For a like-for-like spare, record the catalog number and revision from the nameplate; a current-production equivalent is identified by matching function and ratings.
Manufacturer reference
ABB catalog entry for 1SDA074744R1 identifies the XT2N 125 frame, 100 A TMA trip and three-pole UL/CSA configuration.