| Country of Origin |
India |
| Lead Time |
8 week |
| Made To Order |
No |
| Warranty Return |
Product under warranty must be returned |
| Product Sales Status |
Active |
| Quote Only |
No |
| Stocked At Warehouses |
INABB015EXPU |
| ABB EcoSolutions |
Yes |
| ABB Site Meeting Group Waste To Landfill Target |
UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions |
9AKK108468A2347 |
| Environmental Product Declaration - EPD |
9AKK108468A1890 / 9AKK108468A7793 |
| Extended Product Lifetime |
Product is Modular |
| Recyclability Rate of the Product acc. to EN45555 |
Design for Closing Resource Loops - Standard EN45555 - 55.9 % |
| REACH Declaration |
9AKK108466A1425 |
| RoHS Declaration |
9AKK108466A1424 |
| RoHS Information |
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) |
9AKK108467A5658 |
| Toxic Substances Control Act - TSCA |
9AKK108467A8326 |
| SCIP |
5cab19a8-a211-40c5-bc9a-598007736c08 Italy |
| Environmental Information |
9AKK108467A6707 |
| Order Code US and Canada |
XT1BE3040AFF000XXX |
| E-Number (Finland) |
3638025 |
| E-Number (Norway) |
4309604 |
| EAN |
8015644003302 |
| Minimum Order Quantity |
1 piece |
| Customs Tariff Number |
85362090 |
| Product Net Width |
76.2 mm |
| Product Net Height |
130 mm |
| Product Net Depth / Length |
70 mm |
| Product Net Weight |
1.1 kg |
| Package Level 1 Units |
box 1 piece |
| Package Level 1 Width |
128 mm |
| Package Level 1 Height |
135 mm |
| Package Level 1 Depth / Length |
143 mm |
| Package Level 1 Gross Weight |
1.124 kg |
| Package Level 1 EAN |
8015644003302 |
| Circuit Breaker Type to be Associated |
Power Distribution |
| Product Main Type |
SACE Tmax XT |
| Product Name |
Moulded Case Circuit Breaker |
| Product Type |
Automatic Circuit Breaker |
| Version |
F |
| CAD Dimensional Drawing |
1SDH001295R0008 |
| Connecting Capacity Main Circuit |
Busbar 45.5 ... 80 mm² |
| Current Type |
AC/DC |
| Electrical Durability |
120 cycles per hour / 8000 cycle |
| Mechanical Durability |
240 cycles per hour / 25000 cycle |
| Number of Poles |
3P |
| Opening Time |
CB with SOR 30 ms / CB with UVR 30 ms |
| Order Multiple |
1 piece |
| Power Loss |
at Rated Operating Conditions per Pole 2.6 W |
| Rated Current (I<sub>n</sub>) |
40 A |
| Rated Frequency (f) |
50 / 60 Hz |
| Rated Impulse Withstand Voltage (U<sub>imp</sub>) |
8 kV |
| Rated Instantaneous Short-Circuit Current Setting (I<sub>i</sub>) |
450 A |
| Rated Insulation Voltage (U<sub>i</sub>) |
800 V |
| Rated Operational Voltage |
690 V AC / 500 V DC |
| Rated Service Short-Circuit Breaking Capacity (I<sub>cs</sub>) |
(220 V AC) 25 kA / (230 V AC) 25 kA / (240 V AC) 25 kA / (380 V AC) 18 kA / (415 V AC) 18 kA / (440 V AC) 11.25 kA / (500 V AC) 8 kA / (525 V AC) 6 kA / (690 V AC) 3 kA / (250 V DC) 2 Poles in Series 18 kA / (500 V DC) 3 Poles in Series 18 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (I<sub>cu</sub>) |
(220 V AC) 25 kA / (230 V AC) 25 kA / (240 V AC) 25 kA / (380 V AC) 18 kA / (415 V AC) 18 kA / (440 V AC) 15 kA / (500 V AC) 8 kA / (525 V AC) 6 kA / (690 V AC) 3 kA / (250 V DC) 2 Poles in Series 18 kA / (500 V DC) 3 Poles in Series 18 kA |
| Rated Uninterrupted Current (I<sub>u</sub>) |
160 A |
| Rated Voltage (U<sub>r</sub>) |
690 V |
| Recommended Screw Driver |
Main Circuit M6 |
| Release |
TMD |
| Release Type |
TM |
| Setting Range |
28...40 A |
| Short-Circuit Performance Level |
B |
| Standards |
IEC60947-2 |
| Sub-type |
XT1 |
| Terminal Connection Type |
Front |
| Terminal Type |
Bolt |
| Tightening Torque |
6 N·m |
| ATEX Certificate |
No certification needed |
| Data Sheet, Technical Information |
1SDC210100D0206 / 1SDC210099D0206 |
| Declaration of Conformity - CE |
9AKK106713A5532 |
| GL Certificate |
1SDL000163R0103 |
| LR Certificate |
1SDL000163R0100 |
| UL Certificate |
No certification needed |
| VDE Certificate |
No certification needed |
| Dimension Diagram |
1SDH000719R0100 |
| Mechanical Drawings |
1SDH000719R0100 |
| Wiring Diagram |
1SDM000068R0001 |
| Instructions and Manuals |
1SDH000719R0001 |
| ETIM 9 |
EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 |
EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code |
Q |
| WEEE Category |
5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass |
V11.1 : 27370409 |
40 A (Rated Uninterrupted Current Iu = 160 A).
3 poles (3P).
Thermomagnetic TMD, instantaneous setting 450 A.
690 V AC / 500 V DC.
IEC 60947-2.