ABB product — UA30-30-10 110V 50HZ / 110-120V 60HZ
-->
Product identification
- Model: UA30-30-10 110V 50HZ / 110-120V 60HZ
- Global material number: 1SBL281022R8410
Source: PLC Direct (third-party listing of ABB official product data)
Evidence URL: https://plc-direct.com/products/1sbl281022r8410
Technical specifications
Source: PLC Direct (third-party listing of ABB official product data) — https://plc-direct.com/products/1sbl281022r8410
Dimensions
| Product Net Width |
54 mm |
| Product Net Depth / Length |
108.3 mm |
| Product Net Height |
90 mm |
| Product Net Weight |
0.71 kg |
Technical
| Number of Main Contacts NO |
3 |
| Number of Main Contacts NC |
0 |
| Number of Auxiliary Contacts NO |
1 |
| Number of Auxiliary Contacts NC |
0 |
| Number of Poles |
3P |
| Standards |
IEC/EN 60947-1, IEC/EN 60947-4-1 |
| Rated Operational Voltage |
Auxiliary Circuit 690 V |
| Rated Frequency (f) |
Auxiliary Circuit 50 / 60 Hz |
| Short-Circuit Protective Devices |
Auxiliary Circuit - gG Type Fuses 10 A |
| Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A |
| Mechanical Durability |
10 million |
| Maximum Mechanical Switching Frequency |
3600 cycles per hour |
| Minimum Switching Capacity |
17 / 5 VLT4K |
| Coil Consumption |
Average Holding Value 50 / 60 Hz 12 V·A |
| Power Loss |
at Rated Operating Conditions per Pole 0.1 W |
| Operate Time |
Between Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) |
2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit |
Flexible with Cable End 2.5 ... 10 mm² |
| Connecting Capacity Auxiliary Circuit |
Flexible with Cable End 0.75 ... 2.5 mm² |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Connecting Terminals (delivered in open position) Main Poles |
M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector |
| Terminal Type |
Screw Terminals |
| Product Name |
Block Contactor |
Environmental
| Ambient Air Temperature |
Close to Contactor for Storage -60 ... +80 °C |
| Climatic Withstand |
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Maximum Operating Altitude Permissible |
Without Derating 3000 m |
| Pollution Degree |
3 |
Frequently asked questions
What is the rated supply voltage?
Auxiliary Circuit 690 V
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Operational Voltage" (https://plc-direct.com/products/1sbl281022r8410)
How many poles / contacts does it have?
3
Source: PLC Direct (third-party listing of ABB official product data), field "Number of Main Contacts NO" (https://plc-direct.com/products/1sbl281022r8410)
What is the rated frequency?
Auxiliary Circuit 50 / 60 Hz
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Frequency (f)" (https://plc-direct.com/products/1sbl281022r8410)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Source: PLC Direct (third-party listing of ABB official product data), field "Degree of Protection" (https://plc-direct.com/products/1sbl281022r8410)
What is the power rating?
at Rated Operating Conditions per Pole 0.1 W
Source: PLC Direct (third-party listing of ABB official product data), field "Power Loss" (https://plc-direct.com/products/1sbl281022r8410)
How is it mounted?
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Source: PLC Direct (third-party listing of ABB official product data), field "Mounting on DIN Rail" (https://plc-direct.com/products/1sbl281022r8410)
-->