Product identification
-
Model: TB5600-2ETH
-
China order number: 3ABD00038898
-
Global material number: 1SAP110300R0278
Product description
Terminal base. For AC500 V3. Without slot for communication module. 2 Ethernet interfaces. 1 serial interface. 1 CAN interface (TB5600-2ETH)
Source: ABB official product page
Technical specifications
Source: ABB Data sheet 3ADR010080
Technical data
| Connection of the supply voltage 24 V DC at the terminal base of the processor module |
Removable 5-pin terminal block spring type (3 Technical data)
|
| Melting integral of a fuse at 24 V DC |
Min. 1 A2s 2) (3 Technical data)
|
| Peak inrush current from 24 V DC |
55 A 2) (3 Technical data)
|
| Number of slots for processor modules |
1 (on all terminal bases) (3 Technical data)
|
| Mounting position |
Horizontal or vertical (3 Technical data)
|
Mechanical data
| Mounting |
Horizontal/Vertical (4.5 Mechanical data)
|
| Wiring method |
Spring/screw terminals (4.5 Mechanical data)
|
| Degree of protection |
PLC system: IP 20 ● With all modules or option boards plugged in. ● With all terminals plugged in. ● With all covers closed. (4.5 Mechanical data)
|
| Housing |
Classification V-2 according to UL 94 (4.5 Mechanical data)
|
| Vibration resistance (sinusoidal) acc. to IEC 60068-2-6 |
All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (4.5 Mechanical data)
|
| Shock test acc. to IEC 60068-2-27 |
All three axes 15 g, 11 ms, half-sinusoidal (4.5 Mechanical data)
|
| Mounting Rail Top Hat according to IEC 60715 |
35 mm, depth 7.5 mm or 15 mm (4.5 Mechanical data)
|
| Mounting with screws |
M4 (4.5 Mechanical data)
|
Environmental conditions
| Voltage |
24 V (-15 %, +20 %) (4.1 Environmental conditions)
|
| Protection against reverse polarity |
Yes (4.1 Environmental conditions)
|
| Voltage |
100 V ... 240 V (-15 %, +10 %) (4.1 Environmental conditions)
|
| Frequency |
50/60 Hz (-6 %, +4 %) (4.1 Environmental conditions)
|
| DC supply |
Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 (4.1 Environmental conditions)
|
| AC supply |
Interruption < 0.5 periods, time between 2 interruptions > 1 s (4.1 Environmental conditions)
|
| Operating |
0 °C ... +60 °C: Horizontal mounting of modules. 0 °C ... +40 °C: Vertical mounting of modules. Output load reduced to 50 % per group. (4.1 Environmental conditions)
|
| Storage |
-40 °C ... +70 °C (4.1 Environmental conditions)
|
| Transport |
-40 °C ... +70 °C (4.1 Environmental conditions)
|
| Humidity |
Max. 95 %, without condensation (4.1 Environmental conditions)
|
Additional data
| Radiated emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Conducted emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Electrostatic discharge (ESD) according to IEC 61000-4-2, criterion B |
Air discharge: 8 kV Contact discharge: 6 kV (4.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 2 kV Digital inputs/outputs (24 V DC): 1 kV Digital inputs/outputs (240 V AC): 2 kV Analog inputs/outputs: 1 kV Communication lines shielded: 1 kV (4.4 Electromagnetic compatibility)
|
| High energy transient interference voltages (surge) according to IEC 61000-4-5, criterion B |
Power supply (DC): - Line to ground: 1 kV - Line to line: 0,5 kV Digital inputs/outputs/relay: (24 V DC): - Line to ground: 1 kV (AC): - Line to ground: 2 kV - Line to line: 1 kV Analog inputs/outputs: - Line to ground: 1 kV Communication lines: - Line to ground: 1 kV (4.4 Electromagnetic compatibility)
|
| Influence of radiated disturbances IEC 61000-4-3, criterion A |
Test field strength: 10 V/m (4.4 Electromagnetic compatibility)
|
| Influence of line-conducted interferences IEC 61000-4-6, criterion A |
Test voltage: 10 V (4.4 Electromagnetic compatibility)
|
| Power frequency magnetic fields IEC 61000-4-8, criterion A |
30 A/m 50 Hz 30 A/m 60 Hz (4.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 4 kV Digital inputs/outputs (24 V DC): 2 kV Digital inputs/outputs (240 V AC): 4 kV Analog inputs/outputs: 2 kV Communication lines shielded: 2 kV (5.4 Electromagnetic compatibility)
|
Frequently asked questions
Q: What is the TB5600-2ETH?
A: Terminal base. For AC500 V3. Without slot for communication module. 2 Ethernet interfaces. 1 serial interface. 1 CAN interface (TB5600-2ETH) (ABB official product page)
Q: How many channels or slots does it provide?
A: 1 (on all terminal bases) (Datasheet 3ADR010080, 3 Technical data)
Q: What is the rated supply voltage?
A: Removable 5-pin terminal block spring type (Datasheet 3ADR010080, 3 Technical data)
Q: What is the degree of protection?
A: PLC system: IP 20 ● With all modules or option boards plugged in. ● With all terminals plugged in. ● With all covers closed. (Datasheet 3ADR010080, 4.5 Mechanical data)
Q: How is it mounted?
A: Horizontal or vertical (Datasheet 3ADR010080, 3 Technical data)
Q: What is the housing material?
A: Classification V-2 according to UL 94 (Datasheet 3ADR010080, 4.5 Mechanical data)