ABB product — T4S 250 PR221DS-LS/I In=160 3p F F
-->
Product identification
- Model: T4S 250 PR221DS-LS/I In=160 3p F F
- Global material number: 1SDA054022R1
Source: ABB Product Information System (PIS) - official ABB product data
Evidence URL: https://www.abb.com/global/en/products/1sda054022r1
Technical specifications
Source: ABB Product Information System (PIS) - official ABB product data — https://www.abb.com/global/en/products/1sda054022r1
Environmental
| Environmental Information |
9AKK10103A1057 |
Ordering
| EAN |
8015644551087 |
| Minimum Order Quantity |
1 piece |
| Customs Tariff Number |
85362090 |
Dimensions
| Product Net Width |
105 mm |
| Product Net Height |
205 mm |
| Product Net Depth / Length |
103.5 mm |
| Product Net Weight |
3.5 kg |
Container Information
| Package Level 1 Units |
1 piece |
| Package Level 1 Width |
248 mm |
| Package Level 1 Height |
240 mm |
| Package Level 1 Depth / Length |
285 mm |
| Package Level 1 Gross Weight |
3.5 kg |
| Package Level 1 EAN |
8015644551087 |
Additional Information
| Product Main Type |
SACE Tmax T |
| Product Name |
Moulded Case Circuit Breaker |
| Product Type |
Automatic Circuit Breaker |
| Suitable For |
T4 |
| Suitable for Product Class |
Moulded Case Circuit Breakers |
| Version |
F |
Technical
| Electrical Durability |
8000 cycle |
| Mechanical Durability |
20000 cycle |
| Number of Poles |
3P |
| Power Loss |
at Rated Operating Conditions per Pole 4.4 W |
| Rated Current (In) |
160 A |
| Rated Impulse Withstand Voltage (Uimp) |
8 kV |
| Rated Insulation Voltage (Ui) |
1000 V |
| Rated Operational Voltage |
690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) |
(220 V AC) 85 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) |
(220 V AC) 85 kA |
| Rated Uninterrupted Current (Iu) |
250 A |
| Release |
PR221DS-LS/I |
| Release Type |
EL |
| Short-Circuit Performance Level |
S |
| Standards |
IEC |
| Sub-type |
T4 |
| Terminal Connection Type |
Fixed Circuit-Breakers |
| Test Voltage Max (Utest) |
3500 V |
| Test Voltage at Industrial Frequency for 1 Minute |
3500 V |
Frequently asked questions
What is the rated supply voltage?
8 kV
Source: ABB Product Information System (PIS) - official ABB product data, field "Rated Impulse Withstand Voltage (Uimp)" (https://www.abb.com/global/en/products/1sda054022r1)
What is the rated current?
160 A
Source: ABB Product Information System (PIS) - official ABB product data, field "Rated Current (In)" (https://www.abb.com/global/en/products/1sda054022r1)
How many poles / contacts does it have?
3P
Source: ABB Product Information System (PIS) - official ABB product data, field "Number of Poles" (https://www.abb.com/global/en/products/1sda054022r1)
What is the rated frequency?
3500 V
Source: ABB Product Information System (PIS) - official ABB product data, field "Test Voltage at Industrial Frequency for 1 Minute" (https://www.abb.com/global/en/products/1sda054022r1)
What is the power rating?
at Rated Operating Conditions per Pole 4.4 W
Source: ABB Product Information System (PIS) - official ABB product data, field "Power Loss" (https://www.abb.com/global/en/products/1sda054022r1)
What is the product weight?
3.5 kg
Source: ABB Product Information System (PIS) - official ABB product data, field "Product Net Weight" (https://www.abb.com/global/en/products/1sda054022r1)
-->