ABB product — PSE300-600-70-1
-->
Product identification
- Model: PSE300-600-70-1
- Global material number: 1SFA897114R7001
Source: PLC Direct (third-party listing of ABB official product data)
Evidence URL: https://plc-direct.com/products/1sfa897114r7001
Product description
PSE300-600-70-1 Softstarter - 300 A - 208 ... 600 V AC
Source: ABB official product page (description cross-checked)
Technical specifications
Source: PLC Direct (third-party listing of ABB official product data) — https://plc-direct.com/products/1sfa897114r7001
Dimensions
| Product Net Width |
190 mm |
| Product Net Height |
435 mm |
| Product Net Depth / Length |
237 mm |
| Product Net Weight |
10.6 kg |
Technical
| Rated Operational Voltage |
208 ... 600 V AC |
| Rated Frequency (f) |
50/60 Hz |
| Rated Operational Power - In-Line Connection (Pe) |
(230 V) 90 kW |
| Rated Operational Current - In-Line Connection (Ie) |
300 A |
| Service Factor Percentage |
100 % |
| Overload Protection |
Built-in electronic overload protection |
| Integrated Electronic Overload |
Yes |
| Starting Capacity at Maximum Rated Current Ie |
4xIe for 10s |
| Ramp Time |
0 ... 30 second [unit of time] |
| Initial Voltage During Start |
30 ... 70 % |
| Step Down Voltage Special Ramp |
No % |
| Current Limit Function |
1.5 ... 7xIe |
| Switch for Inside Delta Connection |
No |
| Run Signal Relay |
Yes |
| By-pass Signal Relay |
Yes |
| Fault Signal Relay |
Yes |
| Overload Signal Relay |
Yes |
| Analog Outputs |
4…20 mA |
| Signal Indication Completed Start Ramp (LED) |
Green |
| Signal Indication Ready to Start/Standby ON (LED) |
Green |
| Signal Indication Running R (LED) |
Green |
| Signal Indication Ramping Up/Down (LED) |
Green |
| Signal Indication Protection (LED) |
Yellow |
| Signal Indication Fault (LED) |
Red |
| Communication |
Modbus-RTU |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
| Terminal Type |
Main Circuit: Bars |
| Connecting Capacity Main Circuit |
Hole Diameter 8.5 mm |
| Connecting Capacity Control Circuit |
Rigid 1 x 2.5 mm² |
| Connecting Capacity Supply Circuit |
Rigid 1 x 2.5 |
| Tightening Torque |
Control Circuit 0.5 N·m |
| Product Main Type |
PSE300 |
| Function |
Soft start with torque control |
| Protection Function |
Electronic overload protection, EOL; Locked rotor protection; Current underload protection |
Environmental
| Ambient Air Temperature |
Operation -25 ... +60 °C |
Frequently asked questions
What is the rated supply voltage?
208 ... 600 V AC
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Operational Voltage" (https://plc-direct.com/products/1sfa897114r7001)
What is the rated current?
300 A
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Operational Current - In-Line Connection (Ie)" (https://plc-direct.com/products/1sfa897114r7001)
What is the rated frequency?
50/60 Hz
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Frequency (f)" (https://plc-direct.com/products/1sfa897114r7001)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Source: PLC Direct (third-party listing of ABB official product data), field "Degree of Protection" (https://plc-direct.com/products/1sfa897114r7001)
What is the power rating?
(230 V) 90 kW
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Operational Power - In-Line Connection (Pe)" (https://plc-direct.com/products/1sfa897114r7001)
What is the product weight?
10.6 kg
Source: PLC Direct (third-party listing of ABB official product data), field "Product Net Weight" (https://plc-direct.com/products/1sfa897114r7001)
-->