Product identification
-
Model: PM554-TP-ETH
-
China order number: 3ABD00033168
-
Global material number: 1SAP120600R0071
Product description
PM554-TP-ETH:AC500,Prog.Logic Controller
Source: ABB official product page
Technical specifications
Source: ABB Data sheet 3ADR010065
Technical data
| Power supply / 24 V DC |
100 - 240 V AC (2 Technical data)
|
| Inrush current at nominal voltage / Typ. 3.9 A2s |
Typ. 0.3 A2s (2 Technical data)
|
| Required fuse / 3 A fast |
Max. 10 A (2 Technical data)
|
| - VAR data |
10 kB (2 Technical data)
|
| - VAR_RETAIN data |
1 kB, always buffered in flash (2 Technical data)
|
| - %RB data (persistent) |
1 kB, can be buffered in flash (depending on configuration) (2 Technical data)
|
| - %MB data |
2 kB (PM554 and PM564 types) 64 kB (PM556 and PM566 types) (2 Technical data)
|
| Data buffering |
In flash memory (2 Technical data)
|
| Real-time clock (RTC) |
Optional (2 Technical data)
|
| Battery low indication |
Warning (2 Technical data)
|
| Programming languages |
- Instruction List (IL) - Function Block Diagram (FBD) - Ladder Diagram (LD) - Sequential Function Chart (SFC) - Structured Text (ST) - Continuous Function Chart (CFC) (2 Technical data)
|
| Processor type |
Freescale ARM Processor 32-bit (2 Technical data)
|
| Processor clock speed |
50 MHz (2 Technical data)
|
| Binary |
0.08 ms (2 Technical data)
|
Mechanical data
| Mounting |
Horizontal/Vertical (3.5 Mechanical data)
|
| Wiring method |
Spring/screw terminals (3.5 Mechanical data)
|
| Degree of protection |
PLC system: IP 20 ● with all modules or option boards plugged in ● with all terminals plugged in ● with all covers closed (3.5 Mechanical data)
|
| Housing |
Classification V-2 according to UL 94 (3.5 Mechanical data)
|
| Vibration resistance (sinusoidal) acc. to IEC 60068-2-6 |
All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (3.5 Mechanical data)
|
| Shock test acc. to IEC 60068-2-27 |
All three axes 15 g, 11 ms, half-sinusoidal (3.5 Mechanical data)
|
| Mounting Rail Top Hat according to IEC 60715 |
35 mm, depth 7.5 mm or 15 mm (3.5 Mechanical data)
|
| Mounting with screws |
M4 (3.5 Mechanical data)
|
Environmental conditions
| Voltage |
24 V (-15 %, +20 %) (3.1 Environmental conditions)
|
| Protection against reverse polarity |
Yes (3.1 Environmental conditions)
|
| Voltage |
24 V (-15 %, +10 %) (3.1 Environmental conditions)
|
| Frequency |
50/60 Hz (-6 %, +4 %) (3.1 Environmental conditions)
|
| Voltage |
100 V ... 240 V (-15 %, +10 %) (3.1 Environmental conditions)
|
| DC supply |
Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 (3.1 Environmental conditions)
|
| AC supply |
Interruption < 0.5 periods, time between 2 interruptions > 1 s (3.1 Environmental conditions)
|
| Operating |
0 °C ... +60 °C (horizontal mounting of modules) 0 °C ... +40 °C (vertical mounting of modules and output load reduced to 50 % per group) (3.1 Environmental conditions)
|
| Storage |
-40 °C ... +70 °C (3.1 Environmental conditions)
|
| Transport |
-40 °C ... +70 °C (3.1 Environmental conditions)
|
Additional data
| Radiated emission according to IEC 61000-6-4 CISPR11, class A |
Yes (3.4 Electromagnetic compatibility)
|
| Conducted emission according to IEC 61000-6-4 CISPR11, class A |
Yes (3.4 Electromagnetic compatibility)
|
| Electrostatic discharge (ESD) according to IEC 61000-4-2, criterion B |
Air discharge: 8 kV Contact discharge: 6 kV (3.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 2 kV Digital inputs/outputs (24 V DC): 1 kV Digital inputs/outputs (240 V AC): 2 kV Analog inputs/outputs: 1 kV Communication lines shielded: 1 kV (3.4 Electromagnetic compatibility)
|
| High energy transient interference voltages (surge) according to IEC 61000-4-5, criterion B |
Power supply (DC): - Line to ground: 1 kV - Line to line: 0,5 kV Digital inputs/outputs/relay: (24 V DC): - Line to ground: 1 kV (AC): - Line to ground: 2 kV - Line to line: 1 kV Analog inputs/outputs: - Line to ground: 1 kV Communication lines: - Line to ground: 1 kV (3.4 Electromagnetic compatibility)
|
| Influence of radiated disturbances IEC 61000-4-3, criterion A |
Test field strength: 10 V/m (3.4 Electromagnetic compatibility)
|
| Influence of line-conducted interferences IEC 61000-4-6, criterion A |
Test voltage: 10 V (3.4 Electromagnetic compatibility)
|
| Power frequency magnetic fields IEC 61000-4-8, criterion A |
30 A/m 50 Hz 30 A/m 60 Hz (3.4 Electromagnetic compatibility)
|
Frequently asked questions
Q: What is the PM554-TP-ETH?
A: PM554-TP-ETH:AC500,Prog.Logic Controller (ABB official product page)
Q: What is the rated supply voltage?
A: Typ. 0.3 A2s (Datasheet 3ADR010065, 2 Technical data)
Q: What is the degree of protection?
A: PLC system: IP 20 ● with all modules or option boards plugged in ● with all terminals plugged in ● with all covers closed (Datasheet 3ADR010065, 3.5 Mechanical data)
Q: How is it mounted?
A: Horizontal/Vertical (Datasheet 3ADR010065, 3.5 Mechanical data)
Q: What is the housing material?
A: Classification V-2 according to UL 94 (Datasheet 3ADR010065, 3.5 Mechanical data)
Q: What vibration and shock ratings does it meet?
A: All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (Datasheet 3ADR010065, 3.5 Mechanical data)