ABB product — N40E
-->
Product identification
- Model: N40E
- Global material number: 1SBH141001R8040
Source: ABB official product data (dealer mirror: santaclarasystems.com)
Evidence URL: https://www.santaclarasystems.com/abb/1sbh141001r8040
Technical specifications
Source: ABB official product data (dealer mirror: santaclarasystems.com) — https://www.santaclarasystems.com/abb/1sbh141001r8040
Technical
| Product ID |
1SBH141001R8040 |
| Extended Product Type |
1SBH141001R8040 |
| Product Net Weight |
0.340 kg |
| Product Net Width |
44 mm |
| Product Net Height |
74 mm |
| Product Net Depth |
74 mm |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Ambient Air Temperature |
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C |
| Standards |
Devices complying with international standards IEC 947-5-1 / 947-4-1 and European standards EN 60 947-5-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1 |
| Rated Impulse Withstand Voltage (Uimp) |
8 kV |
| Rated Insulation Voltage (Ui) |
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V |
| Terminal Type |
Screw Terminals |
| Rated Frequency (f) |
Supply Circuit 50 Hz Supply Circuit 60 Hz |
| Number of Auxiliary Contacts NO |
4 |
| Number of Auxiliary Contacts NC |
0 |
| GOST Certificate |
GOST_POCCFRME01B03022 |
| Maximum Operating Altitude Permissible |
3000 m |
| Rated Control Circuit Voltage (Uc) |
50 Hz 220 … 230 V 60 Hz 230 … 240 V |
| Climatic Withstand |
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Maximum Mechanical Switching Frequency |
6000 cycles per hour |
| Connecting Capacity Auxiliary Circuit |
Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² |
| Operate Time |
Between Coil Energization and NO Contact Closing 10 ... 26 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms |
| GL Certificate |
DNV-GL_TAE00000TY |
| Short-Circuit Protective Devices |
gG Type Fuses 10 A |
| Coil Operating Limits |
(acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C |
| EAN |
3471522012807 |
| Rated Operational Voltage |
Main Circuit 690 V |
| Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-5-1, q = 40 °C 16 A |
| Rated Operational Current AC-15 (Ie) |
(220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A |
| Rated Short-time Withstand Current (Icw) |
for 0.1 s 140 A for 1 s 100 A |
| Rated Operational Current DC-13 (Ie) |
(125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A |
| Resistance to Shock acc. to IEC 60068-2-27 |
Shock Direction: A 20 g Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g |
| Instructions and Manuals |
FPTC407721P0001 |
| BV Certificate |
BV_2634H09651C0 |
| CB Certificate |
CB_FR_602227B |
| CCC Certificate |
CCC_2003010304088235 |
| cUL Certificate |
UL_110105E48139A |
| Data Sheet, Technical Information |
1SBC100122C0202_Ch03 |
| Declaration of Conformity - CE |
1SBD250808U1000 |
| DNV Certificate |
DNV-GL_TAE00000TY |
| LR Certificate |
LRS_9830010E2 |
| RINA Certificate |
RINA_ELE128713XG002 |
| RMRS Certificate |
RMRS_0507015250 |
| UNSPSC |
39121500 |
| Object Classification Code |
K |
Frequently asked questions
What is the rated supply voltage?
8 kV
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Rated Impulse Withstand Voltage (Uimp)" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
What is the rated current?
acc. to IEC 60947-5-1, q = 40 °C 16 A
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Conventional Free-air Thermal Current (Ith)" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
How many poles / contacts does it have?
4
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Number of Auxiliary Contacts NO" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
What is the rated frequency?
Supply Circuit 50 Hz Supply Circuit 60 Hz
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Rated Frequency (f)" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Degree of Protection" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
What is the product weight?
0.340 kg
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Product Net Weight" (https://www.santaclarasystems.com/abb/1sbh141001r8040)
-->