ABB product — AS09-30-01-20
-->
Product identification
- Model: AS09-30-01-20
- Global material number: 1SBL101001R2001
Source: PLC Direct (third-party listing of ABB official product data)
Evidence URL: https://plc-direct.com/products/1sbl101001r2001
Technical specifications
Source: PLC Direct (third-party listing of ABB official product data) — https://plc-direct.com/products/1sbl101001r2001
Dimensions
| Product Net Width |
45 mm |
| Product Net Depth / Length |
72.5 mm |
| Product Net Height |
68 mm |
| Product Net Weight |
0.22 kg |
Technical
| Number of Main Contacts NO |
3 |
| Number of Main Contacts NC |
0 |
| Number of Auxiliary Contacts NO |
0 |
| Number of Auxiliary Contacts NC |
1 |
| Standards |
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14 |
| Rated Operational Voltage |
Auxiliary Circuit 690 V |
| Rated Frequency (f) |
Auxiliary Circuit 50 / 60 Hz |
| Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 155 A |
| Maximum Electrical Switching Frequency |
(AC-1) 600 cycles per hour |
| Maximum Mechanical Switching Frequency |
3600 cycles per hour |
| Power Loss |
at Rated Operating Conditions AC-1 per Pole 1 W |
| Operate Time |
Between Coil De-energization and NC Contact Closing 7 ... 22 ms |
| Connecting Capacity Main Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Wire Stripping Length |
Auxiliary Circuit 9 mm |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Tightening Torque |
Auxiliary Circuit 1 N·m |
| Terminal Type |
Screw Terminals |
| Product Name |
Block Contactor |
Environmental
| Ambient Air Temperature |
Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C |
| Climatic Withstand |
Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible |
Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 |
Closed, Shock Direction: B1 10 g |
| Resistance to Vibrations |
3g Closed Position & 2g Open Position 5 ... 300 Hz |
Frequently asked questions
What is the rated supply voltage?
Auxiliary Circuit 690 V
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Operational Voltage" (https://plc-direct.com/products/1sbl101001r2001)
How many poles / contacts does it have?
3
Source: PLC Direct (third-party listing of ABB official product data), field "Number of Main Contacts NO" (https://plc-direct.com/products/1sbl101001r2001)
What is the rated frequency?
Auxiliary Circuit 50 / 60 Hz
Source: PLC Direct (third-party listing of ABB official product data), field "Rated Frequency (f)" (https://plc-direct.com/products/1sbl101001r2001)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Source: PLC Direct (third-party listing of ABB official product data), field "Degree of Protection" (https://plc-direct.com/products/1sbl101001r2001)
What is the power rating?
at Rated Operating Conditions AC-1 per Pole 1 W
Source: PLC Direct (third-party listing of ABB official product data), field "Power Loss" (https://plc-direct.com/products/1sbl101001r2001)
What is the product weight?
0.22 kg
Source: PLC Direct (third-party listing of ABB official product data), field "Product Net Weight" (https://plc-direct.com/products/1sbl101001r2001)
-->