ABB product — AF80-30-00-41
-->
Product identification
- Model: AF80-30-00-41
- Global material number: 1SBL397001R4100
Source: ABB official product data (dealer mirror: santaclarasystems.com)
Evidence URL: https://www.santaclarasystems.com/abb/1sbl397001r4100
Technical specifications
Source: ABB official product data (dealer mirror: santaclarasystems.com) — https://www.santaclarasystems.com/abb/1sbl397001r4100
Technical
| Product ID |
1SBL397001R4100 |
| Extended Product Type |
1SBL397001R4100 |
| Product Net Weight |
1.220 kg |
| Product Net Width |
70 mm |
| Product Net Height |
125.5 mm |
| Product Net Depth |
116 mm |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
| Ambient Air Temperature |
Close to Contactor for Storage -60...+80 °C Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C Close to Contactor without Thermal O/L Relay -40 ... +70 °C |
| Rated Impulse Withstand Voltage (Uimp) |
8 kV |
| Rated Insulation Voltage (Ui) |
acc. to UL/CSA 600 V acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| Terminal Type |
Screw Terminals |
| Rated Frequency (f) |
Main Circuit 50 / 60 Hz |
| Number of Auxiliary Contacts NO |
0 |
| Number of Auxiliary Contacts NC |
0 |
| Connecting Capacity Main Circuit |
Flexible with Insulated Ferrule 1/2x 6...50 mm² Flexible with Ferrule 1/2x 6...50 mm² Rigid 1x 6...70 mm² Rigid 2x 6...50 mm² |
| Maximum Operating Altitude Permissible |
3000 m |
| Rated Control Circuit Voltage (Uc) |
50 Hz 24 ... 60 V 60 Hz 24 ... 60 V |
| Climatic Withstand |
Category B according to IEC 60947-1 Annex Q |
| Tightening Torque UL/CSA |
Control Circuit 11 in·lb Main Circuit 53 in·lb |
| Maximum Mechanical Switching Frequency |
3600 cycles per hour |
| Operate Time |
Between Coil De-energization and NC Contact Closing 19 ... 105 ms Between Coil De-energization and NO Contact Opening 17 ... 100 ms Between Coil Energization and NC Contact Opening 38 ... 95 ms Between Coil Energization and NO Contact Closing 42 ... 100 ms |
| Wire Stripping Length |
Main Circuit 17 mm |
| Number of Main Contacts NO |
3 |
| GL Certificate |
DNV-GL_E13871 |
| Number of Main Contacts NC |
0 |
| Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A |
| Connecting Capacity Control Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
| Horsepower Rating UL/CSA |
(120 V AC) Single Phase 7-1/2 Hp (240 V AC) Single Phase 15 Hp (200 ... 208 V AC) Three Phase 25 Hp (220 ... 240 V AC) Three Phase 30 Hp (440 ... 480 V AC) Three Phase 60 Hp (550 ... 600 V AC) Three Phase 75 Hp |
| General Use Rating UL/CSA |
(600 V AC) 105 A |
| EAN |
3471523132900 |
| Rated Operational Voltage |
Main Circuit 690 V |
| Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 130 A |
| Rated Operational Current AC-1 (Ie) |
(690 V) 40 °C 125 A (690 V) 60 °C 100 A (690 V) 70 °C 85 A |
| Rated Operational Current AC-3 (Ie) |
(220 / 230 / 240 V) 60 °C 80 A (380 / 400 V) 60 °C 80 A (415 V) 60 °C 80 A (440 V) 60 °C 80 A (500 V) 60 °C 65 A (690 V) 60 °C 49 A (1000 V) 60 °C 25 A |
| Rated Operational Power AC-3 (Pe) |
(220 / 230 / 240 V) 22 kW (380 / 400 V) 37 kW (400 V) 37 kW (415 V) 45 kW (440 V) 45 kW (500 V) 45 kW (690 V) 45 kW |
| Maximum Electrical Switching Frequency |
AC-1 600 cycles per hour AC-2 / AC-4 150 cycles per hour AC-3 1200 cycles per hour |
| Resistance to Vibrations acc. to IEC 60068-2-6 |
5...300 Hz 3 g closed position / 3 g open position |
| Resistance to Shock acc. to IEC 60068-2-27 |
Closed, Shock Direction: A 25 g Closed, Shock Direction: B1 25 g Closed, Shock Direction: B2 15 g Closed, Shock Direction: C1 25 g Closed, Shock Direction: C2 25 g Open, Shock Direction: B1 5 g |
| Instructions and Manuals |
1SBC101036M6801 |
| ABS Certificate |
ABS_15-GE1349500-PDA_90682247 |
| BV Certificate |
BV_2634H36994A |
| CB Certificate |
CB_SE-77417M1 |
| CCC Certificate |
CCC_2013010304646569 |
| cUL Certificate |
UL_20130926-E312527_14_1 |
| Data Sheet, Technical Information |
1SBC100173C0201 |
| Declaration of Conformity - CE |
1SBD250000U1000 |
| DNV Certificate |
DNV-GL_E13871 |
| EAC Certificate |
EAC_RU C-FR ME77 B01010 |
| LR Certificate |
LRS_1300087E1 |
| RINA Certificate |
RINA_ELE084013XG |
| RMRS Certificate |
RMRS_1400682124 |
| UNSPSC |
39121529 |
| Object Classification Code |
Q |
Frequently asked questions
What is the rated supply voltage?
8 kV
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Rated Impulse Withstand Voltage (Uimp)" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
What is the rated current?
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 130 A
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Conventional Free-air Thermal Current (Ith)" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
How many poles / contacts does it have?
0
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Number of Auxiliary Contacts NO" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
What is the rated frequency?
Main Circuit 50 / 60 Hz
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Rated Frequency (f)" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Degree of Protection" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
What is the power rating?
(120 V AC) Single Phase 7-1/2 Hp (240 V AC) Single Phase 15 Hp (200 ... 208 V AC) Three Phase 25 Hp (220 ... 240 V AC) Three Phase 30 Hp (440 ... 480 V AC) Three Phase 60 Hp (550 ... 600 V AC) Three Phase 75 Hp
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Horsepower Rating UL/CSA" (https://www.santaclarasystems.com/abb/1sbl397001r4100)
-->