ABB product — A16-40-00
-->
Product identification
- Model: A16-40-00
- Global material number: 1SBL181201R8000
Source: ABB official product data (dealer mirror: santaclarasystems.com)
Evidence URL: https://www.santaclarasystems.com/abb/1sbl181201r8000
Technical specifications
Source: ABB official product data (dealer mirror: santaclarasystems.com) — https://www.santaclarasystems.com/abb/1sbl181201r8000
Technical
| Product ID |
1SBL181201R8000 |
| Extended Product Type |
1SBL181201R8000 |
| Product Net Weight |
0.340 kg |
| Product Net Width |
44 mm |
| Product Net Height |
74 mm |
| Product Net Depth |
74 mm |
| Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Ambient Air Temperature |
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C |
| Standards |
Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1 |
| Rated Impulse Withstand Voltage (Uimp) |
8 kV |
| Rated Insulation Voltage (Ui) |
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V |
| Terminal Type |
Screw Terminals |
| Number of Auxiliary Contacts NO |
0 |
| Number of Auxiliary Contacts NC |
0 |
| Mechanical Durability |
10 million |
| Connecting Capacity Main Circuit |
Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² |
| GOST Certificate |
GOST_POCCFRME77B07175 |
| Maximum Operating Altitude Permissible |
3000 m |
| Rated Control Circuit Voltage (Uc) |
50 Hz 220 … 230 V 60 Hz 230 … 240 V |
| Climatic Withstand |
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Maximum Mechanical Switching Frequency |
3600 cycles per hour |
| Connecting Capacity Auxiliary Circuit |
Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² |
| Operate Time |
Between Coil Energization and NO Contact Closing 10 ... 26 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Number of Main Contacts NO |
4 |
| GL Certificate |
DNV-GL_TAE00000TX |
| Number of Main Contacts NC |
0 |
| Short-Circuit Protective Devices |
gG Type Fuses 32 A |
| Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A |
| Coil Operating Limits |
(acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C |
| Connecting terminals (delivered in open position) Main poles |
M 3.5 (+,-) pozidriv 2 screws with cable clamp |
| EAN |
3471522051806 |
| Rated Operational Voltage |
Main Circuit 690 V |
| Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 30 A |
| Rated Operational Current AC-1 (Ie) |
(690 V) 40 °C 30 A (690 V) 55 °C 27 A (690 V) 70 °C 23 A |
| Rated Operational Current AC-3 (Ie) |
(220 / 230 / 240 V) 55 °C 17 A (380 / 400 V) 55 °C 17 A (415 V) 55 °C 17 A (440 V) 55 °C 16 A (500 V) 55 °C 14 A (690 V) 55 °C 10 A |
| Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1 |
8 x Ie AC-3 |
| Rated Making Capacity AC-3 acc. to IEC 60947-4-1 |
10 x Ie AC-3 |
| Maximum Electrical Switching Frequency |
AC-1 600 cycles per hour AC-2 / AC-4 300 cycles per hour AC-3 1200 cycles per hour |
| Resistance to Shock acc. to IEC 60068-2-27 |
Shock Direction: A 20 g Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g |
| Instructions and Manuals |
FPTC407721P0001 |
| BV Certificate |
BV_2634H07559D0 |
| CCC Certificate |
CCC_2013010304615753 CCC_2004010309130463 |
| cUL Certificate |
UL_20160205-E312527-10-2 |
| Data Sheet, Technical Information |
1SBC100122C0202_Ch02 |
| Declaration of Conformity - CE |
1SBD250802U1000 |
| DNV Certificate |
DNV-GL_TAE00000TX |
| EAC Certificate |
EAC_RU C-FR ME77 B01010 |
| LOVAG Certificate |
LOVAG_FR97081 |
| LR Certificate |
LRS_9830011E4 |
| RINA Certificate |
RINA_ELE400503CS1 |
| RMRS Certificate |
RMRS_0507015250 |
| E-nummer |
3228024 |
| UNSPSC |
39121529 |
| Object Classification Code |
Q |
Frequently asked questions
What is the rated supply voltage?
8 kV
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Rated Impulse Withstand Voltage (Uimp)" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
What is the rated current?
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 30 A
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Conventional Free-air Thermal Current (Ith)" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
How many poles / contacts does it have?
0
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Number of Auxiliary Contacts NO" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
What is the rated frequency?
3600 cycles per hour
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Maximum Mechanical Switching Frequency" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
What is the degree of protection?
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Degree of Protection" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
What is the product weight?
0.340 kg
Source: ABB official product data (dealer mirror: santaclarasystems.com), field "Product Net Weight" (https://www.santaclarasystems.com/abb/1sbl181201r8000)
-->