Product identification
-
Model: AI561
-
China order number: 3ABD10094787
-
Global material number: 1TNE968902R1101
Product description
Analog input module. 4 AI: U, I (AI561)
Source: ABB official product page
Technical specifications
Source: ABB Data sheet 3ADR010031
Technical data
| Connections |
Terminal 19 for L+ (+24 V DC) and terminal 20 for M (0 V) (3.1 Technical data of the module)
|
| Rated value |
24 V DC (3.1 Technical data of the module)
|
| Current consumption via L+ terminal |
0.1 A; 0.02 A (version E0 or later) (3.1 Technical data of the module)
|
| Inrush current (at power up) |
Typ. 0.1 A2s; Max. 0.16 A2s (3.1 Technical data of the module)
|
| Max. ripple |
5 % (3.1 Technical data of the module)
|
| Protection against reversed voltage |
Yes (3.1 Technical data of the module)
|
| Protection fuse for L+ |
Yes, external additional fuse recommended (3.1 Technical data of the module)
|
| Current consumption from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/ communication interface module |
Ca. 5 m A (3.1 Technical data of the module)
|
| Galvanic isolation |
No (3.1 Technical data of the module)
|
| Surge-voltage (max.) |
35 V DC for 0.5 s (3.1 Technical data of the module)
|
| Max. power dissipation within the module |
2.7 W 1 W (version E0 or later) (3.1 Technical data of the module)
|
| Weight |
Ca. 120 g (3.1 Technical data of the module)
|
| Mounting position |
Horizontal or vertical (3.1 Technical data of the module)
|
| Cooling |
The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet. (3.1 Technical data of the module)
|
Mechanical data
| Mounting |
Horizontal/Vertical (4.5 Mechanical data)
|
| Wiring method |
Spring/screw terminals (4.5 Mechanical data)
|
| Degree of protection |
PLC system: IP 20 ● with all modules or option boards plugged in ● with all terminals plugged in ● with all covers closed (4.5 Mechanical data)
|
| Housing |
Classification V-0 according to UL 94 (4.5 Mechanical data)
|
| Vibration resistance (sinusoidal) acc. to IEC 60068-2-6 |
All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (4.5 Mechanical data)
|
| Shock test acc. to IEC 60068-2-27 |
All three axes 15 g, 11 ms, half-sinusoidal (4.5 Mechanical data)
|
| Mounting Rail Top Hat according to IEC 60715 |
35 mm, depth 7.5 mm or 15 mm (4.5 Mechanical data)
|
| Mounting with screws |
M4 (4.5 Mechanical data)
|
Environmental conditions
| Voltage |
24 V (-15 %, +20 %) (4.1 Environmental conditions)
|
| Protection against reverse polarity |
Yes (4.1 Environmental conditions)
|
| Voltage |
24 V (-15 %, +10 %) (4.1 Environmental conditions)
|
| Frequency |
50/60 Hz (-6 %, +4 %) (4.1 Environmental conditions)
|
| Voltage |
100 V ... 240 V (-15 %, +10 %) (4.1 Environmental conditions)
|
| DC supply |
Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 (4.1 Environmental conditions)
|
| AC supply |
Interruption < 0.5 periods, time between 2 interruptions > 1 s (4.1 Environmental conditions)
|
| Operating |
0 °C ... +60 °C (horizontal mounting of modules) 0 °C ... +40 °C (vertical mounting of modules and output load reduced to 50 % per group) (4.1 Environmental conditions)
|
| Storage |
-40 °C ... +70 °C (4.1 Environmental conditions)
|
| Transport |
-40 °C ... +70 °C (4.1 Environmental conditions)
|
Additional data
| Radiated emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Conducted emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Electrostatic discharge (ESD) according to IEC 61000-4-2, criterion B |
Air discharge: 8 kV Contact discharge: 6 kV (4.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 2 kV Digital inputs/outputs (24 V DC): 1 kV Digital inputs/outputs (240 V AC): 2 kV Analog inputs/outputs: 1 kV Communication lines shielded: 1 kV (4.4 Electromagnetic compatibility)
|
| High energy transient interference voltages (surge) according to IEC 61000-4-5, criterion B |
Power supply (DC): - Line to ground: 1 kV - Line to line: 0,5 kV Digital inputs/outputs/relay: (24 V DC): - Line to ground: 1 kV (AC): - Line to ground: 2 kV - Line to line: 1 kV Analog inputs/outputs: - Line to ground: 1 kV Communication lines: - Line to ground: 1 kV (4.4 Electromagnetic compatibility)
|
| Influence of radiated disturbances IEC 61000-4-3, criterion A |
Test field strength: 10 V/m (4.4 Electromagnetic compatibility)
|
| Influence of line-conducted interferences IEC 61000-4-6, criterion A |
Test voltage: 10 V (4.4 Electromagnetic compatibility)
|
| Power frequency magnetic fields IEC 61000-4-8, criterion A |
30 A/m 50 Hz 30 A/m 60 Hz (4.4 Electromagnetic compatibility)
|
Frequently asked questions
Q: What is the AI561?
A: Analog input module. 4 AI: U, I (AI561) (ABB official product page)
Q: What is the current rating?
A: 0.1 A; 0.02 A (version E0 or later) (Datasheet 3ADR010031, 3.1 Technical data of the module)
Q: What is the degree of protection?
A: PLC system: IP 20 ● with all modules or option boards plugged in ● with all terminals plugged in ● with all covers closed (Datasheet 3ADR010031, 4.5 Mechanical data)
Q: How is it mounted?
A: Horizontal or vertical (Datasheet 3ADR010031, 3.1 Technical data of the module)
Q: What is the housing material?
A: Classification V-0 according to UL 94 (Datasheet 3ADR010031, 4.5 Mechanical data)
Q: What vibration and shock ratings does it meet?
A: All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (Datasheet 3ADR010031, 4.5 Mechanical data)