Product identification
-
Model: AI523-XC
-
China order number: 3ABD00029584
-
Global material number: 1SAP450300R0001
Product description
Analog input module. 16 AI: U, I, RTD, DI (AI523-XC)
Source: ABB official product page
Technical specifications
Source: ABB Data sheet 3ADR010029
Technical data
| Rated value |
24 V DC (3.1 Technical data of the module)
|
| Max. ripple |
5 % (3.1 Technical data of the module)
|
| Protection against reversed voltage |
Yes (3.1 Technical data of the module)
|
| Rated protection fuse on UP |
10 A fast (3.1 Technical data of the module)
|
| Galvanic isolation |
Yes, per module (3.1 Technical data of the module)
|
| From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/communication interface module |
Ca. 2 m A (3.1 Technical data of the module)
|
| From UP at normal operation / with outputs |
0.15 A + output loads (3.1 Technical data of the module)
|
| Inrush current from UP (at power up) |
0.050 A2s (3.1 Technical data of the module)
|
| Max. length of analog cables, conductor cross section > 0.14 mm2 |
100 m (3.1 Technical data of the module)
|
| Weight |
300 g (3.1 Technical data of the module)
|
| Mounting position |
Horizontal mounting or Vertical mounting with derating (output load reduced to 50 % at +40 °C per group) (3.1 Technical data of the module)
|
| Cooling |
The natural convection cooling must not be hindered by cable ducts or other parts in the control cabinet. (3.1 Technical data of the module)
|
| Internal power supply |
Via the I/O bus interface (I/O bus) (3.1 Technical data of the module)
|
| External power supply |
Via the terminals ZP and UP (process voltage 24 V DC) (3.1 Technical data of the module)
|
Mechanical data
| Mounting |
Horizontal/Vertical (4.5 Mechanical data)
|
| Wiring method |
Spring/screw terminals (4.5 Mechanical data)
|
| Degree of protection |
PLC system: IP 20 ● With all modules or option boards plugged in. ● With all terminals plugged in. ● With all covers closed. (4.5 Mechanical data)
|
| Housing |
Classification V-2 according to UL 94 (4.5 Mechanical data)
|
| Vibration resistance (sinusoidal) acc. to IEC 60068-2-6 |
All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (4.5 Mechanical data)
|
| Shock test acc. to IEC 60068-2-27 |
All three axes 15 g, 11 ms, half-sinusoidal (4.5 Mechanical data)
|
| Mounting Rail Top Hat according to IEC 60715 |
35 mm, depth 7.5 mm or 15 mm (4.5 Mechanical data)
|
| Mounting with screws |
M4 (4.5 Mechanical data)
|
Environmental conditions
| Voltage |
24 V (-15 %, +20 %) (5.1 Environmental conditions)
|
| Protection against reverse polarity |
Yes (5.1 Environmental conditions)
|
| Voltage |
100 V ... 240 V (-15 %, +10 %) (5.1 Environmental conditions)
|
| Frequency |
50/60 Hz (-6 %, +4 %) (5.1 Environmental conditions)
|
| DC supply |
Interruption < 10 ms, time between 2 interruptions > 1 s, PS2 (5.1 Environmental conditions)
|
| AC supply |
Interruption < 0.5 periods, time between 2 interruptions > 1 s (5.1 Environmental conditions)
|
| Operating |
-40 °C ... +70 °C -40 °C ... 0 °C: Due to the LCD technology, the display might respond very slowly. -40 °C ... +40 °C: Vertical mounting of modules possible, output load limited to 50 % per group +60 °C ... +70 °C with the following deratings: ● System is limited to maximum 2 communication modules per terminal base... (5.1 Environmental conditions)
|
| Storage / Transport |
-40 °C ... +85 °C (5.1 Environmental conditions)
|
| Humidity |
Operating / Storage: 100 % r. H. with condensation (5.1 Environmental conditions)
|
| Air pressure |
Operating: -1000 m .... 5000 m (1080 h Pa ... 620 h Pa) > 2000 m (< 795 h Pa): ● Maximum operating temperature must be reducted by 10 K for each 1000 m exceeding 2000 m. ● I/O module relay contacts must be operated with 24 V nominal only. (5.1 Environmental conditions)
|
Additional data
| Radiated emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Conducted emission according to IEC 61000-6-4 CISPR11, class A |
Yes (4.4 Electromagnetic compatibility)
|
| Electrostatic discharge (ESD) according to IEC 61000-4-2, criterion B |
Air discharge: 8 kV Contact discharge: 6 kV (4.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 2 kV Digital inputs/outputs (24 V DC): 1 kV Digital inputs/outputs (240 V AC): 2 kV Analog inputs/outputs: 1 kV Communication lines shielded: 1 kV (4.4 Electromagnetic compatibility)
|
| High energy transient interference voltages (surge) according to IEC 61000-4-5, criterion B |
Power supply (DC): - Line to ground: 1 kV - Line to line: 0,5 kV Digital inputs/outputs/relay: (24 V DC): - Line to ground: 1 kV (AC): - Line to ground: 2 kV - Line to line: 1 kV Analog inputs/outputs: - Line to ground: 1 kV Communication lines: - Line to ground: 1 kV (4.4 Electromagnetic compatibility)
|
| Influence of radiated disturbances IEC 61000-4-3, criterion A |
Test field strength: 10 V/m (4.4 Electromagnetic compatibility)
|
| Influence of line-conducted interferences IEC 61000-4-6, criterion A |
Test voltage: 10 V (4.4 Electromagnetic compatibility)
|
| Power frequency magnetic fields IEC 61000-4-8, criterion A |
30 A/m 50 Hz 30 A/m 60 Hz (4.4 Electromagnetic compatibility)
|
| Fast transient interference voltages (burst) according to IEC 61000-4-4, criterion B |
Power supply (DC): 4 kV Digital inputs/outputs (24 V DC): 2 kV Digital inputs/outputs (240 V AC): 4 kV Analog inputs/outputs: 2 kV Communication lines shielded: 2 kV (5.4 Electromagnetic compatibility)
|
Frequently asked questions
Q: What is the AI523-XC?
A: Analog input module. 16 AI: U, I, RTD, DI (AI523-XC) (ABB official product page)
Q: What is the degree of protection?
A: PLC system: IP 20 ● With all modules or option boards plugged in. ● With all terminals plugged in. ● With all covers closed. (Datasheet 3ADR010029, 4.5 Mechanical data)
Q: How is it mounted?
A: Horizontal mounting or Vertical mounting with derating (output load reduced to 50 % at +40 °C per group) (Datasheet 3ADR010029, 3.1 Technical data of the module)
Q: What is the housing material?
A: Classification V-2 according to UL 94 (Datasheet 3ADR010029, 4.5 Mechanical data)
Q: What vibration and shock ratings does it meet?
A: All three axes 2 Hz ... 8.4 Hz, 3.5 mm peak, 8.4 Hz ... 150 Hz, 1 g (Datasheet 3ADR010029, 4.5 Mechanical data)
Q: What is the weight?
A: 300 g (Datasheet 3ADR010029, 3.1 Technical data of the module)