| Applicable PLC |
FX0N, FX1N, FX2N, FX3G, FX3U, FX2NC, FX3GC, FX3UC [Connecting to the connector-type PLC] The FX2NC-CNV-IF is required to connect the FX2NC. The FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect the FX3GC/FX3UC. |
| Number of occupied I/O points |
8 points (Taken from either the input or output points of the PLC.) |
| Mass (weight) |
0.3 kg |
| Analog input - Analog input range - Voltage input |
-10 V to +10 V DC(Input resistance 200 kΩ) |
| Analog input - Analog input range - Current input |
-20 mA to +20 mA DC (Input resistance 250 Ω) |
| Analog input - Number of input channels |
4 channels |
| Analog input - Absolute maximum input - Voltage input |
±15 V |
| Analog input - Absolute maximum input - Current input |
±32 mA |
| Analog input - Input characteristics |
The input mode (voltage/current input) can be set for each channel. |
| Analog input - Digital output |
11 bits binary + sign 1 bit |
| Analog input - Resolution - Voltage input |
5 mV (10 V × 1/2000) |
| Analog input - Resolution - Current input |
20 μA (20 mA × 1/1000) |
| Analog input - Total accuracy - Voltage input |
±1% (±0.2 V) for 20 V full scale |
| Analog input - Total accuracy - Current input |
±1% (±0.4 mA) for 40 mA full scale |
| Power supply specifications |
/ 5 V DC 30 mA (internal power supply from PLC main unit) 24 V DC ±10% 55 mA (External power supply) |
| Ambient temperature |
0 to 55°C (32 to 131 °F) when operating and -25 to 75°C (-13 to 167 °F) when stored |
| Ambient humidity |
5 to 95%RH (no condensation) when operating |
| Vibration resistance - Installed on DIN rail - Frequency: 10 to 57 Hz |
Half amplitude: 0.035 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) |
| Vibration resistance - Installed on DIN rail - Frequency: 57 to 150 Hz |
Acceleration: 4.9 m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) |
| Vibration resistance - Direct installing - Frequency: 10 to 57 Hz |
Half amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) |
| Vibration resistance - Direct installing - Frequency: 57 to 150 Hz |
Acceleration: 9.8m/s 2 Sweep Count for X, Y, Z: 10 times (80 min in each direction)***** |
| Shock resistance |
147 m/s 2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z |
| Noise resistance |
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz |
| Dielectric withstand voltage |
Between batch of all terminals and ground terminal: 500 V AC for 1 min |
| Insulation resistance |
Between batch of all terminals and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester |
| Grounding |
Class D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly. |
| Working atmosphere |
Free from corrosive or flammable gas and excessive conductive dusts |
| Working altitude |
2000 m or less Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC. |
FX0N, FX1N, FX2N, FX3G, FX3U, FX2NC, FX3GC, FX3UC [Connecting to the connector-type PLC] The FX2NC-CNV-IF is required to connect the FX2NC. The FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect the