EL9210 | EtherCAT Terminal, potential supply, 24 V DC, with diagnostics, replaceable fuses
The EL9210 potential feed terminal with fuse and diagnostics enables the setup of different potential groups with a fused standard voltage of 24 V DC. ...
Technical Specifications
EL9210 Technology potential supply terminal with diagnostics and fuse Current load ≤ 10 A Power LED green Defect LED red Renewed infeed yes Current consumption E-bus typ. 90 mA Nominal voltage 24 V DC Integrated fine-wire fuse …6.3 A Electrical isolation 500 V (E-bus/field potential) Diagnostics in the process image yes Reported to E-bus yes Connection facility to additional power contact 1 Bit width in the process image 2 Housing width 12 mm Side by side mounting on EtherCAT Terminals with power contact yes Side by side mounting on EtherCAT Terminals without power contact yes Weight approx. 55 g Operating temperature -25…+55°C Storage temperature -40…+85°C Approvals/markings CE, CCC, UL, ATEX, IECEx, DNV Ex marking ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc Technical data Housing data To top Housing data EL-12-6pin Design form compact terminal housing with signal LEDs Material