EL6631-0010 | EtherCAT Terminal, 2-port communication interface, PROFINET RT, device
The EL6631 PROFINET RT controller (master) terminal supports the complete real-time function (RT) as well as extensive diagnostic possibilities. All services...
Technical Specifications
EL6631-0010 Technology PROFINET RT Number of channels 1 Number of ports 2 (switched) Fieldbus PROFINET RT device Max. process data size 1 kbyte input/1 kbyte output data Ethernet interface 100BASE-TX Ethernet with 2 x RJ45 Cable length up to 100 m twisted pair Hardware diagnostics status LEDs Power supply via the E-bus Electrical isolation 500 V (E-bus/Ethernet) Protocol RT Configuration via EtherCAT master Current consumption E-bus typ. 400 mA Special features LLDP, SNMP, Conformance Class B, max. 15 RT devices, min. 1 ms RT cycle Weight approx. 75 g Operating temperature 0…55°C Storage temperature -25…+85°C Relative humidity 95%, no condensation Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27 EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4 Protect. rating/installation pos. IP20/see documentation Approvals/markings CE, CCC, UL, ATEX, IECEx Ex marking ATEX:
Availability: regular delivery (not recommended for new projects) | recommended alternative: EL6633-0010