ABB · SACE Tmax XT2L · Moulded Case Circuit Breaker

1SDA067648R1 is an ABB SACE Tmax XT2L 160 moulded case circuit breaker (MCCB), fixed three-pole version with front terminals and a thermomagnetic TMA R 160 release — rated 160 A and 120 kA ultimate breaking capacity at 415 V AC.

  • Catalog number1SDA067648R1
  • FrameXT2L 160
  • Rated current In160 A
  • Breaking capacity Icu120 kA @ 415 V AC

Specifications

Electrical
Rated current In 160 A
Rated operational voltage Ue 690 V AC / 500 V DC
Rated insulation voltage Ui 1000 V (IEC 60947-2)
Rated impulse withstand Uimp 8 kV (IEC 60947-2)
Breaking capacity Icu (415 V AC) 120 kA
Breaking capacity Icu (690 V AC) 18 kA
Number of poles 3P
Release TMA R 160 thermomagnetic (Ir 160 A, Ii 800...1600 A)
Mechanical
Version Fixed
Terminals Front terminals
Dimensions (H × W × D) 130 × 90 × 82.5 mm
Approx. weight 1.1–1.4 kg (per ABB/distributor data)
Environment & compliance
Operating temperature -25...+70 °C
Enclosure rating IP20 (higher ratings with terminals/accessories per catalogue)
Standards IEC 60947-2
Certifications CE, LR, GL

Values follow the official ABB SACE Tmax XT catalogue data for this catalog number; parameters not confirmed for this variant are omitted rather than estimated.

Model comparison in the same family

ABB SACE Tmax XT2 160-frame variants
Catalog number Release Breaking capacity Icu @415 V Poles
1SDA067648R1 — XT2L 160 TMA (this page) TMA thermomagnetic 120 kA 3P
1SDA067715R1 — XT2V 160 TMA TMA thermomagnetic 150 kA 4P
XT2N 160 Ekip LSI (1SDA067071R1) Ekip LSI electronic 36 kA 3P
XT2N 160 TMA (e.g. 1SDA067020R1) TMA thermomagnetic 36 kA 3P

Where it sits in the power distribution system

The XT2L 160 is the high breaking-capacity member of the ABB SACE Tmax XT2 160-frame family. This catalog number protects a three-phase feeder or main incomer where the prospective short-circuit current is beyond what an XT2N (36 kA) can handle: the TMA thermomagnetic release holds a fixed 160 A thermal threshold with an adjustable magnetic pick-up of 800...1600 A. Terminals land on the front for panel wiring without rear access. Record the catalog number and revision from the nameplate of the installed unit before specifying a like-for-like spare.

Before you specify

  • Breaking capacity. Confirm the prospective fault current at the installation point does not exceed 120 kA at 415 V AC (18 kA at 690 V AC); downstream coordination depends on it.
  • Poles. This is the 3-pole version — match it to a three-phase three-wire circuit. For circuits with a switched neutral, use a 4P variant.
  • Release. TMA R 160 gives a fixed 160 A thermal setting and an adjustable magnetic pick-up of 800...1600 A; verify against the cable protection study.
  • Mounting. Fixed body with front terminals — confirm panel depth and terminal clearances before ordering.

Technical FAQ

Q.What is 1SDA067648R1?

It is the ABB catalog number for the SACE Tmax XT2L 160 TMA 160-1600 fixed 3-pole moulded case circuit breaker with front terminals — a 160 A MCCB with 120 kA ultimate breaking capacity at 415 V AC.

Q.What is the difference between XT2L and XT2N?

Same 160-class frame and footprint, different breaking capacity: XT2L reaches 120 kA Icu at 415 V AC, while the XT2N version of the same frame is rated 36 kA. Choose XT2L where the prospective short-circuit current exceeds the XT2N rating.

Q.Which release does this breaker use?

The TMA R 160 thermomagnetic release: thermal protection is fixed at 160 A, and the magnetic (instantaneous) pick-up is adjustable between 800 and 1600 A.

Q.How is this unit mounted and connected?

Fixed mounting with front terminals (bolt/screw connection). Confirm the panel layout and terminal shrouds before ordering a like-for-like spare.

Standard (US & Canada, tracked courier): delivered in 5–8 business days. In-stock items are processed within 2–4 business days. USD 25 flat rate on orders under $500.00; free on orders of $500.00 and above.

Express (DHL Express / FedEx International): upgraded expedited delivery in 2–4 business days. The Express surcharge is calculated at checkout based on destination and order weight.

Non-Stock / On-Order items ship on request: dispatch time is confirmed before your order — see our Shipping Policy. Shipping charges and available services are displayed at checkout. See the Shipping Policy for details.

Every product is covered by a 12-month seller warranty provided by SHLY-PLC, effective from the date of delivery, against defects in materials and workmanship under normal use.

This warranty does not cover damage from misuse, improper installation, power surges, neglect, unauthorized repair, or normal wear and tear. See our Return Policy for warranty-claim instructions.

★★★★★

No reviews yet. Be the first to review this product!