ET 200PA SMART, analog input 0/4 - 20 mA 8 AI, redundancy, 1 x 20-pole, IM 650-8PH required
Product Type: Industrial Automation Component
General
| Article number |
6ES7650-8AK60-0AA0 |
Product function
Load voltage L+
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
Input current
| from load voltage L+ (without load), max. |
20 mA |
| from backplane bus 5 V DC, max. |
120 mA |
Power supply to the transmitters
| ● present |
Yes |
| ● Rated value (DC) |
24 V |
| ● short-circuit proof |
Yes; Short-circuit current approx. 40 mA to 60 mA |
Power loss
Analog inputs
| Number of analog inputs |
8 |
Input ranges (rated values), currents
| ● 0 to 20 mA |
Yes |
| — Input resistance (0 to 20 mA) |
150 Ω |
| ● -20 mA to +20 mA |
Yes |
| — Input resistance (-20 mA to +20 mA) |
150 Ω |
| ● 4 mA to 20 mA |
Yes |
| — Input resistance (4 mA to 20 mA) |
150 Ω |
Cable length
Analog value generation for the inputs
| Measurement principle |
Sigma Delta |
Integration and conversion time/resolution per channel
| ● Resolution with overrange (bit including sign), max. |
16 bit; 15 bit + sign |
| ● Integration time, parameterizable |
Yes |
| ● Integration time (ms) |
16.6 ms @ 60 Hz, 20 ms @ 50 Hz, 100 ms @ 10 Hz |
| ● Basic conversion time, including integration time (ms) |
55 ms @ 60 Hz, 65 ms @ 50 Hz, 305 ms @ 10 Hz |
| ● Basic execution time of the module (all channels released) |
520 ms; 440 ms @ 60 Hz, 520 ms @ 50 Hz, 2 440 ms @ 10 Hz |
Smoothing of measured values
| ● Parameterizable |
Yes; in 4 stages |
| ● Step: None |
Yes; 1x cycle time |
| ● Step: low |
Yes; 4x cycle time |
| ● Step: Medium |
Yes; 32x cycle time |
| ● Step: High |
Yes; 64x cycle time |
Connection of signal encoders
| ● for current measurement as 2-wire transducer |
Yes |
| ● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies
| Linearity error (relative to input range), (+/-) |
0.01 % |
| Temperature error (relative to input range), (+/-) |
0.001 %/K |
| Crosstalk between the inputs, min. |
70 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) |
0.01 % |
Operational error limit in overall temperature range
| ● Current, relative to input range, (+/-) |
0.15 % |
Basic error limit (operational limit at 25 °C)
| ● Current, relative to input range, (+/-) |
0.1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
| ● Series mode interference (peak value of interference < rated value of input range), min. |
40 dB |
| ● Common mode interference, min. |
100 dB |
Interrupts/diagnostics/status information
| Status indicator |
No |
| Diagnostics function |
Yes; Parameterizable |
Alarms
| ● Diagnostic alarm |
Yes; Parameterizable |
Diagnoses
| ● Diagnostic information readable |
Yes |
Diagnostics indication LED
| ● Group error SF (red) |
Yes |
Potential separation analog inputs
| ● between the channels |
No |
| ● between the channels and backplane bus |
Yes |
| ● Between the channels and load voltage L+ |
Yes; only for 4-wire transducer |
Permissible potential difference
| between M internally and the inputs |
75 V DC/60 V AC |
Isolation
| Isolation tested with |
500 V DC |
Ambient temperature during operation
| ● min. |
0 °C |
| ● max. |
60 °C; if the device is installed horizontally |
Connection method
| required front connector |
20-pin |
Dimensions
| Width |
40 mm |
| Height |
125 mm |
| Depth |
117 mm |
Weights
Classifications
| Version |
Classification |
| eClass |
16 |
| eClass |
14 |
| eClass |
12 |
| eClass |
9.1 |
| eClass |
9 |
| eClass |
8 |
| eClass |
7.1 |
| eClass |
6 |
| ETIM |
10 |
| ETIM |
9 |
| ETIM |
8 |
| ETIM |
7 |
| IDEA |
4 |
| UNSPSC |
15 |
General Product Approval
| EU declaration of conformity |
Yes |
| China RoHS |
Yes |
| Manufacturer Declaration |
Yes |
For use in hazardous locations
| ATEX |
Yes |
| IECEx |
Yes |
| CCC |
Yes |
| last modified: |
7/3/2026 |
Applications
This Industrial Automation Component is designed for industrial automation applications, offering reliable performance and compatibility with Siemens automation systems. Suitable for manufacturing, process control, and building automation environments.