{"product_id":"kl3312","title":"Beckhoff KL3312 | Beckhoff Bus Terminals","description":"\u003ch2\u003eKL3312 | Bus Terminal, 2-channel analog input, temperature, thermocouple, 16 bit\u003c\/h2\u003e \u003cp\u003eThe KL3312 analog input terminal allows thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the...\u003c\/p\u003e \u003ch3\u003eTechnical Specifications\u003c\/h3\u003e \u003cp\u003eKL3312 Number of inputs 2 Power supply via the K-bus Technology 2-wire Thermocouple sensor types types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement Measuring range in the range defined in each case for the sensor (default setting: type K; -100…+1370°C); mV measurement: ±30 mV…±120 mV Connection technology 2-wire Conversion time ~ 250 ms Wire break detection yes Resolution 0.1°C per digit Measurement error\/uncertainty Electrical isolation 500 V (K-bus\/signal voltage) Current consumption power contacts – (no power contacts) Current consumption K-bus typ. 65 mA Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control\/status optional) Configuration no address setting, configuration via Bus Coupler or controller Weight approx. 70 g Operating temperature 0…55°C Storage temperature -25…+85°C Relative humidity 95%, no condensation Vibration\/shock resistan\u003c\/p\u003e \u003cp\u003e\u003cstrong\u003eAvailability:\u003c\/strong\u003e regular delivery\u003c\/p\u003e","brand":"Beckhoff","offers":[{"title":"New","offer_id":46136701649149,"sku":"KL3312","price":388.34,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0747\/5665\/3309\/files\/kl3312.jpg?v=1784999097","url":"https:\/\/shly-plc.com\/products\/kl3312","provider":"Lianyou PLC","version":"1.0","type":"link"}