{"product_id":"kl2622","title":"KL2622 Beckhoff","description":"\u003ch2\u003eKL2622 | Bus Terminal, 2-channel relay output, 230 V AC, 30 V DC, 5 A, without power contacts\u003c\/h2\u003e\n\u003cp\u003eThe KL2622 output terminal has two relays, each with a single contact, and can be used to switch devices requiring mains power and operating at up to 230...\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cp\u003eKL2622 Number of outputs 2 x make contacts Nominal voltage 230 V AC\/30 V DC Load type ohmic, inductive, lamp load Max. output current 5 A per channel Switching current 5 A AC\/DC (ohmic)\/2 A AC\/DC (inductive) Ohmic switching current 5 A AC\/DC Inductive switching current 2 A AC\/DC Minimum permitted load 10 mA at 5 V DC Lamp test, electronic ballast max. 5 A starting current (4 x 58 W) Electrical isolation 500 V (K-bus\/field potential) Current consumption power contacts – Current consumption K-bus typ. 85 mA Bit width in the process image 2 outputs Operating cycles mech. (min.) 2 x 10 7 Operating cycles electr. (min.) 1 x 10 5 (5 A\/30 V DC) Configuration no address or configuration setting Special features potential-free contacts Weight approx. 80 g Operating temperature -25…+60°C Storage temperature -40…+85°C Relative humidity 95%, no condensation Vibration\/shock resistance conforms to EN\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eAvailability:\u003c\/strong\u003e regular delivery\u003c\/p\u003e","brand":"Beckhoff","offers":[{"title":"Never Used Surplus","offer_id":70984840839421,"sku":"KL2622","price":170.63,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0747\/5665\/3309\/files\/kl2622.jpg?v=1785000045","url":"https:\/\/shly-plc.com\/products\/kl2622","provider":"Lianyou PLC","version":"1.0","type":"link"}