{"product_id":"el3312","title":"Beckhoff EL3312 | Beckhoff Ethercat Terminals","description":"\u003ch2\u003eEL3312 | EtherCAT Terminal, 2-channel analog input, temperature, thermocouple, 16 bit\u003c\/h2\u003e \u003cp\u003eThe EL3312 analog input terminal allows thermocouples to be connected directly. The EtherCAT Terminal's circuit can operate thermocouple sensors using ...\u003c\/p\u003e \u003ch3\u003eTechnical Specifications\u003c\/h3\u003e \u003cp\u003eEL3312 Number of inputs 2 Power supply via the E-bus Distributed clocks – Input filter cut-off frequency typ. 1 kHz Connection technology 2-wire Conversion time approx. 1.2 s up to 7 ms, depending on configuration and filter setting, default: approx. 125 ms Voltage measurement ±30\/±60\/±75 mV Resolution 16 bit, representation adjustable: 0.1\/0.01°C or 1\/2\/4 µV per digit Temperature measurement (thermocouple) type B, C, E, J, K, L, N, R, S, T, U (default setting: type K) Measurement uncertainty (temperature measurement) at 23°C ambient temperature, with internal cold junction, according type: B: ±8.5°C; C: ±6.2°C; E: ±2.5°C; J: ±2.7°C; K: ±3°C; L: ±2.3°C; N: ±3°C; R: ±6.7°C; S: ±7.1°C; T: ±2.9°C; U: ±2.5°C; for further details see documentation Measurement uncertainty (voltage measurement) at ±75 mV, 23°C ambient temperature: Electrical isolation 500 V (E-bus\/signal voltage) Current consum\u003c\/p\u003e \u003cp\u003e\u003cstrong\u003eAvailability:\u003c\/strong\u003e regular delivery\u003c\/p\u003e","brand":"Beckhoff","offers":[{"title":"New","offer_id":46136709316861,"sku":"EL3312","price":388.34,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0747\/5665\/3309\/files\/el3312.jpg?v=1784998436","url":"https:\/\/shly-plc.com\/products\/el3312","provider":"Lianyou PLC","version":"1.0","type":"link"}