{"product_id":"3um161-6","title":"B\u0026R 3UM161-6 | Industrial Automation Component","description":"\u003cp\u003e\u003cstrong\u003eCategory:\u003c\/strong\u003e To Confirm\u003c\/p\u003e\n\u003cp\u003e2005 universal mixed module, 1 x 4 analog inputs ±10 V, 14-bit, 1 x 3 analog outputs ±10 V, 12-bit, 1 x 14 digital inputs 24 VDC, 1 ms, 1 digital output 24 VDC, 2 A, 500 µs, 1 digital output 24 VDC, 10 mA, 10 µs, both outputs usable as inputs, order 2x TB718 terminal blocks separately!.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eShort description\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eI\/O module = 14 digital inputs, 2 digital outputs, 4 analog inputs, 3 analog outputs, potentiometer power supply, special functions\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eGeneral information\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eDiagnostics\u003c\/li\u003e\n\u003cli\u003ePower supply for digital inputs = Yes, using LED status indicator and software\u003c\/li\u003e\n\u003cli\u003eDigital outputs = Yes, using LED status indicator\u003c\/li\u003e\n\u003cli\u003ePower consumption\u003c\/li\u003e\n\u003cli\u003e24 VDC = 4.0 W (+1.5 W for potentiometer power supply)\u003c\/li\u003e\n\u003cli\u003e5 VDC = 2.0 W\u003c\/li\u003e\n\u003cli\u003eTotal = 6.0 W\u003c\/li\u003e\n\u003cli\u003eElectrical isolation\u003c\/li\u003e\n\u003cli\u003eChannel - Channel = No\u003c\/li\u003e\n\u003cli\u003eChannel - PLC = Yes\u003c\/li\u003e\n\u003cli\u003ePotentiometer power supply - PLC = Yes\u003c\/li\u003e\n\u003cli\u003eAnalog - Potentiometer power supply = No\u003c\/li\u003e\n\u003cli\u003eDigital - Analog = Yes\u003c\/li\u003e\n\u003cli\u003eCertifications\u003c\/li\u003e\n\u003cli\u003eCE = Yes\u003c\/li\u003e\n\u003cli\u003eUKCA = Yes\u003c\/li\u003e\n\u003cli\u003eUL = cULus E115267 Industrial control equipment\u003c\/li\u003e\n\u003cli\u003eStatus indicators = Converter function, configuration per comparator, power supply for digital inputs, I\/O function per digital channel\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003ePotentiometer power supply\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eVoltage = ±10 V\u003c\/li\u003e\n\u003cli\u003eLoad = 4 x 1 kΩ parallel, total max. ±80 mA\u003c\/li\u003e\n\u003cli\u003eShort-circuit proof = Yes\u003c\/li\u003e\n\u003cli\u003eBasic accuracy = ±0.4% at 25°C\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eDigital inputs\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eInput filter\u003c\/li\u003e\n\u003cli\u003eHardware = ≤1 ms\u003c\/li\u003e\n\u003cli\u003eSoftware = -\u003c\/li\u003e\n\u003cli\u003eQuantity = 14 (+2 if the digital outputs are used as digital inputs)\u003c\/li\u003e\n\u003cli\u003eNominal voltage = 24 VDC\u003c\/li\u003e\n\u003cli\u003eInput circuit = Sink or source\u003c\/li\u003e\n\u003cli\u003eAdditional functions = Event counting, period measurement, latch input (comparator input)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eAnalog inputs\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eQuantity = 4\u003c\/li\u003e\n\u003cli\u003eInput = ±10 V\u003c\/li\u003e\n\u003cli\u003eInput type = Differential input\u003c\/li\u003e\n\u003cli\u003eDigital converter resolution = 14-bit\u003c\/li\u003e\n\u003cli\u003eConversion time = \u0026lt;45 µs for all inputs\u003c\/li\u003e\n\u003cli\u003eOutput format = INT\u003c\/li\u003e\n\u003cli\u003eInput impedance in signal range = 10 MΩ\u003c\/li\u003e\n\u003cli\u003eInput protection = Protection against wiring with supply voltage\u003c\/li\u003e\n\u003cli\u003eBasic accuracy = ±0.05% at 25°C\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eDigital outputs\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eQuantity = 2\u003c\/li\u003e\n\u003cli\u003eNominal voltage = 24 VDC\u003c\/li\u003e\n\u003cli\u003eNominal output current = 10 mA to 2 A\u003c\/li\u003e\n\u003cli\u003eTotal nominal current = 2.01 A\u003c\/li\u003e\n\u003cli\u003eOutput circuit = Source\u003c\/li\u003e\n\u003cli\u003eOutput protection = Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply\u003c\/li\u003e\n\u003cli\u003eSensor power supply = External\u003c\/li\u003e\n\u003cli\u003eAdditional functions = Fast comparator output (10 µs), both outputs can also be used as digital inputs\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eAnalog outputs\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eQuantity = 3\u003c\/li\u003e\n\u003cli\u003eOutput = ±10 V\u003c\/li\u003e\n\u003cli\u003eDigital converter resolution = 12-bit\u003c\/li\u003e\n\u003cli\u003eConversion time = \u0026lt;45 µs for all outputs\u003c\/li\u003e\n\u003cli\u003eSwitch on\/off behavior = Internal enable relay for startup and errors\u003c\/li\u003e\n\u003cli\u003eOutput protection = Protection against wiring with supply voltage, short-circuit proof\u003c\/li\u003e\n\u003cli\u003eBasic accuracy = ±0.05% at 25°C\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eOperating conditions\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eDegree of protection per EN 60529 = IP20\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eAmbient conditions\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eTemperature\u003c\/li\u003e\n\u003cli\u003eOperation = 0 to 60°C\u003c\/li\u003e\n\u003cli\u003eStorage = -25 to 70°C\u003c\/li\u003e\n\u003cli\u003eRelative humidity\u003c\/li\u003e\n\u003cli\u003eOperation = 5 to 95%\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cstrong\u003eMechanical properties\u003c\/strong\u003e\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003eDimensions\u003c\/li\u003e\n\u003cli\u003eWidth = System 2005 single-width\u003c\/li\u003e\n\u003cli\u003eCan be installed on\u003c\/li\u003e\n\u003cli\u003eBase unit = Yes\u003c\/li\u003e\n\u003cli\u003eExpansion unit = Yes\u003c\/li\u003e\n\u003cli\u003eNote = Order 2x TB718 terminal blocks separately\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"B\u0026R","offers":[{"title":"New","offer_id":46160970711293,"sku":"3UM161-6","price":2081.37,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0747\/5665\/3309\/files\/br_brand_generic_3UM161-6.png?v=1785721150","url":"https:\/\/shly-plc.com\/products\/3um161-6","provider":"Lianyou PLC","version":"1.0","type":"link"}